UPS5000-S-(50 kVA-300 kVA)
User Manual
Step 4 Press and hold down the BATT START button on the bypass module for at least 2
seconds. The system automatically enters the battery cold start status. The LCD
displays the Huawei logo and an initialization progress bar.
Step 5 After LCD initialization, start the inverter.
----End
5.4 Transferring to Bypass Mode
Before shutting down the inverter, ensure that the bypass is normal. If the bypass
is not normal, after the inverter is shut down, the UPS supplies no power, and the
loads shut down.
Shut down the UPS inverter. Shut down the inverter on the LCD or WebUI, and the
UPS transfers to bypass mode.
5.5 Setting ECO Mode
Prerequisites
The system is working in inverter mode.
Context
●
●
●
●
●
●
Issue 11 (2020-12-07)
NO TICE
NO TE
If the inverter is shut down when the input voltage or frequency exceeds the specified
threshold, the UPS supplies no power, and the loads shut down.
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
energy saving is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass is disconnected, the UPS transfers to normal mode.
Both a single UPS and the parallel system support the ECO mode for higher
efficiency.
To avoid frequent transfer between ECO mode and normal mode, do not set
the ECO mode when the bypass input is unstable or is sensitive to load
changes.
ECO mode is not recommended when the load is less than 10%.
Before transferring the UPS to ECO mode, ensure that the bypass module
works properly.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
228