Huawei UPS5000-S Series User Manual page 69

50 kva-300 kva
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(50 kVA-300 kVA)
User Manual
Table 3-5 Power cable terminal requirements for the 300 kVA cabinet
Port
Recommended
Description
Connection
Method
Mains input
Crimped OT
terminals
Bypass input
Crimped OT
terminals
Battery input
Crimped OT
terminals
Output
Crimped OT
terminals
PE
Crimped OT
terminals
Table 3-6 Recommended upstream input and downstream output circuit breakers
Model
UPS5000-S-200K-
SM/FM
UPS5000-S-300K-
SM/FMT
Issue 11 (2020-12-07)
Bolt
Specifications
M12
M12
M12
M12
M12
UPS Capacity
50 kVA
100 kVA
150 kVA
200 kVA
250 kVA
Copyright © Huawei Technologies Co., Ltd.
Bolt Hole
Diameter
13.5 mm
13.5 mm
13.5 mm
13.5 mm
13.5 mm
Component
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
3 Installation
Bolt
Torque
Length
45 mm
46 N·m
45 mm
46 N·m
45 mm
46 N·m
45 mm
46 N·m
30 mm
46 N·m
a
Specifications
160 A/3P
100 A/3P
100 A/3P
250 A/3P
160 A/3P
160 A/3P
320 A/3P
250 A/3P
250 A/3P
400 A/3P
400 A/3P
400 A/3P
630 A/3P
400 A/3P
59

Advertisement

Table of Contents
loading

Table of Contents