Starting the UPS on the Old WebUI
Step 1 Open a browser (Internet Explorer 11 for example) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
then click OK.
Figure 5-4 Setting the Internet options
Step 3 In the address box of the browser, enter https://
Step 4 Enter the correct user name and password and click Login.
Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON,
and confirm the operation to start the inverter.
Issue 11 (2020-12-07)
NO TE
If the power module receives a startup command when it cannot be started, the startup
command will be kept for 1 minute. If the startup command is not cleared within 1 minute
(for example, other faults occur on the module, or you perform shutdown or rectify faults)
and the module can be started, the module responds to the startup command.