Huawei UPS5000-S Series User Manual page 162

50 kva-300 kva
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(50 kVA-300 kVA)
User Manual
Figure 4-23 System settings 2
Figure 4-24 System settings 3
Item
Single/
Parallel
Requisite
modules
Redundant
modules
Working
mode
Issue 11 (2020-12-07)
NO TE
If the battery type is lead-acid battery, you can set Batt. temp. sensor [B_TEMP].
Description
Specifies whether the UPS
works in single mode or
parallel mode.
Matches the system capacity.
Set this parameter based on
load capacity and
redundancy requirements.
UPS working mode
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Single
Single, Parallel
N/A
N/A
0
0–19
Normal mode
Normal mode,
ECO, Self-load
mode,
Converter
mode
152