UPS5000-S-(50 kVA-300 kVA)
User Manual
Item
Battery
appearance
Battery
operating
temperature
Charge
voltage of
battery string
Issue 11 (2020-12-07)
Expected Result
1. The surface is clean and
tidy without stains.
2. The battery terminals are
intact.
3. Batteries are free from
damage and cracks.
4. Batteries are free from acid
leakage.
5. Batteries are not deformed
or bulged.
1. The ambient battery
temperature is 25±5°C.
2. The battery operating
temperature is lower than
battery temperature +20°C.
3. Battery charge and
discharge conditions meet
the requirements specified
in the battery
specifications.
● Equalized charging voltage:
(2.35 V/cell ±1%) x Single
battery voltage/2 x Number
of batteries in a battery
string
● Float charging voltage:
(2.25 V/cell ±1%) x Single
battery voltage/2 x Number
of batteries in a battery
string
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
If the battery appearance is
abnormal, contact Huawei
technical support.
1. Identify the cause of an
abnormal battery operating
temperature.
2. If the fault persists, contact
Huawei technical support.
1. If the voltage drop between
the battery string output
terminals and the battery
input terminals at the UPS
side is greater than 1% of
the battery string voltage,
check whether the cable
between the battery string
and the UPS is excessively
long, or the cable diameter
is excessively small.
2. Check whether the
equalized charging voltage
and float charging voltage
are correctly set for the
UPS.
3. If the fault persists, contact
Huawei technical support.
248