3.6.11 Clear Program
PROGRAMMING
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option.
1=PASSWORD CHANGE
This will cause the LCD to display the following screens:
2=CLEAR PROGRAM
3=LOAD PROGRAM
Programming Screen #4
Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all
general system programming options and all programmed addressable devices from the
nonvolatile memory of the FACP. This function is useful when the control panel is first
installed, prior to autoprogramming. Note that it is necessary to autoprogram after using
the Clear Whole System function.
See Page
Pressing 2, for All Loops while viewing the Clear Program Screen #1, will clear all
programming related to all SLC loops and connected addressable devices.
Pressing 3, for Loop 1 while viewing the Clear Program Screen #1, will clear only the
programming related to SLC Loop 1 and the connected addressable devices.
Pressing 1, for Loop 2 while viewing the Clear Program Screen #2, will clear only the
programming related to SLC Loop 2 and the connected addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a
warning to the user by prompting with the following display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2
will prevent programming from being cleared.
@@@CLEAR@PROGRAM
1=WHOLE@SYSTEM
2=ALL@LOOPS
3=LOOP1
Clear Program Screen #1
@@@CLEAR@PROGRAM
1=LOOP2
Clear Program Screen #2
@@@@@@WARNING!
@@SYSTEM@CHANGE
@@@@@PROCEED?
1=YES@@@@@@@@@@@2=NO
Need help?
Do you have a question about the Unimode 9600 and is the answer not in the manual?
Questions and answers