Zone; Silence Inhibited; Synced Type - ADT Unimode 9600 Installation And Operating Instruction

Adt addressable fire alarm control panel programming, installation, maintenance and operating instruction manual
Table of Contents

Advertisement

NAC #

1=ZONE

00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
NAC #
1=SYNC TYPE
NAC Screen #4
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½
second off
Two Stage - 20 ppm (pulse-per-minute) for five minutes followed by on steady
3.6.4.5.6 Zone
@@ZONE@ASSIGNMENT
Z00@Z**@Z**@Z**@Z**
Zone Screen

3.6.4.5.7 Silence Inhibited

3.6.4.5.8 Synced Type

@@@@@NAC@SYNC@TYPE
1=SYSTEM@SENSOR
2=WHEELOCK
3=GENTEX