Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 212

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

TABLE
ACDT_CFG
EXV Superheat Deadband
Auto-Comp Suct.Pres Drop
Auto-Comp DS SP Drop
MLV/HGBP DP Drop
Low Charge Alert Cutoff
High Charge Alert Cutoff
Min Charge SST
ACTUATOR
Econ 1 Out Ser Number 1
Econ 1 Out Ser Number 2
Econ 1 Out Ser Number 3
Econ 1 Out Ser Number 4
Ecn1 Out Ctl Angl Lo Lmt
Econ 2 Ret Ser Number 1
Econ 2 Ret Ser Number 2
Econ 2 Ret Ser Number 3
Econ 2 Ret Ser Number 4
Ecn2 Ret Ctl Angl Lo Lmt
Humd Serial Number 1
Humd Serial Number 2
Humd Serial Number 3
Humd Serial Number 4
Humd Ctrl Angle Lo Limit
Hydronic Ht.Serial Num.1
Hydronic Ht.Serial Num.2
Hydronic Ht.Serial Num.3
Hydronic Ht.Serial Num.4
Hydr.Ht.Ctl.Ang Lo Limit
Econ 3 Out Ser Number 1
Econ 3 Out Ser Number 2
Econ 3 Out Ser Number 3
Econ 3 Out Ser Number 4
Ecn3 Out Ctl Angl Lo Lmt
ALLM
SPT lo alert limit/occ
SPT hi alert limit/occ
SPT lo alert limit/unocc
SPT hi alert limit/unocc
EDT lo alert limit/occ
EDT hi alert limit/occ
EDT lo alert limit/unocc
EDT hi alert limit/unocc
RAT lo alert limit/occ
RAT hi alert limit/occ
RAT lo alert limit/unocc
RAT hi alert limit/unocc
OAT low alert limit
OAT high alert limit
RARH low alert limit
RARH high alert limit
OARH low alert limit
OARH high alert limit
SP low alert limit
SP high alert limit
BP low alert limit
BP high alert limit
IAQ high alert limit
BP__
Building Press. Config
Building Pressure Sensor
Bldg. Press. (+/-) Range
Building Pressure Setp.
BP Setpoint Offset
VFD Fire Speed
VFD Minimum Speed
VFD Maximum Speed
APPENDIX B — CCN TABLES (CONT)
SERVICE-CONFIG TABLES
DISPLAY NAME
RANGE
UNITS
deltaF
deltaF
deltaF
deltaF
deltaF
deltaF
deltaF
degF
degF
degF
degF
degF
degF
degF
degF
degF
degF
degF
degF
degF
degF
%
%
%
%
in H2O
in H2O
in H2O
in H2O
Disable/Enable
in H2O
in H2O
in H2O
%
%
%
212
POINT NAME
DEFAULT
AC_SH_DB
2
AC_SP_DR
3
AC_DS_SP
2.5
AC_MLVDR
5
AC_CH_LO
-3
AC_CH_HI
1
AC_SST_M
40
ECN1_SN1
0
ECN1_SN2
0
ECN1_SN3
0
ECN1_SN4
0
ECONCALM
85
ECN2_SN1
0
ECN2_SN2
0
ECN2_SN3
0
ECN2_SN4
0
ECN2CALM
85
HUMD_SN1
0
HUMD_SN2
0
HUMD_SN3
0
HUMD_SN4
0
HUMDCALM
85
HTCL_SN1
0
HTCL_SN2
0
HTCL_SN3
0
HTCL_SN4
0
HTCLCALM
85
ECN3_SN1
0
ECN3_SN2
0
ECN3_SN3
0
ECN3_SN4
0
ECN3CALM
85
SPLO
60
SPHO
85
SPLU
45
SPHU
100
SALO
40
SAHO
100
SALU
40
SAHU
100
RALO
60
RAHO
90
RALU
40
RAHU
100
OATL
-40
OATH
150
RRHL
0
RRHH
100
ORHL
0
ORHH
100
SPL
0
SPH
2
BPL
-0.25
BPH
0.25
IAQH
1200
BLDG_CFG
0
BPSENS
Enable
BP_RANGE
0.25
BPSP
0.05
BPSO
0.05
BLDGPFSO
100
BLDGPMIN
10
BLDGPMAX
100

Advertisement