Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 188

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
COOL (cont)
HMZR
HUMIDIMIZER
CAPC
HumidiMizer Capacity
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
RHV
HumidiMizer 3-way Valve
C.CPT
Cooling Control Point
EDT
Evaporator Discharge Temp
H.CPT
Heating Control Point
LAT
Leaving Air Temperature
EXVS
EXVS INFORMATION
Circuit A EXV 1 Position
A1.EX
A2.EX
Circuit A EXV 2 Position
Circuit B EXV 1 Position
B1.EX
B2.EX
Circuit B EXV 2 Position
Cir A EXV1 Superheat Tmp
SH.A1
SH.A2
Cir A EXV2 Superheat Tmp
Cir B EXV1 Superheat Tmp
SH.B1
SH.B2
Cir B EXV2 Superheat Tmp
EXVS CONTROL INFORMATION
CTRL
C.SHS
EXV Superheat Ctrl SP
EXV SH Flooding Ctrl SP
C.FLS
C.XMP
CompCir EXV ctrl Min%
EXV PID Ctrl Prop. Gain
C.EXP
C.EXT
EXV Ctrl Integrat. Time
C.EXM
Cir Strt EXV Mn Ctrl Pos
VFDS
VFD INFORMATION
S.VFD
SUPPLY FAN VFD (VFD 1)
SPD
VFD1 Actual Speed %
RPM
VFD1 Actual Motor RPM
FREQ
VFD1 Actual Motor Freq
AMPS
VFD1 Actual Motor Amps
TORQ
VFD1 Actual Motor Torque
PWR
VFD1 Actual Motor Power
VDC
VFD1 DC Bus Voltage
V.OUT
VFD1 Output Voltage
TEMP
VFD1 Transistor Temp (C)
RUN.T
VFD1 Cumulative Run Time
VFD1 Cumulative kWh
KWH
LFC
VFD1 Last Fault Code
EXHAUST FAN VFD (VFD 2)
E.VFD
SPD
VFD2 Actual Speed %
VFD2 Actual Motor RPM
RPM
FREQ
VFD2 Actual Motor Freq
VFD2 Actual Motor Amps
AMPS
TORQ
VFD2 Actual Motor Torque
VFD2 Actual Motor Power
PWR
VDC
VFD2 DC Bus Voltage
VFD2 Output Voltage
V.OUT
TEMP
VFD2 Transistor Temp (C)
RUN.T
VFD2 Cumulative Run Time
KWH
VFD2 Cumulative kWh
LFC
VFD2 Last Fault Code
O.VFD
OUTDOOR FAN VFD
SPD.A
MtrMaster A Commanded %
SPD.B
MtrMaster B Commanded %
TRIP
MODE TRIP HELPER
UN.C.S
Unoccup. Cool Mode Start
UN.C.E
Unoccup. Cool Mode End
OC.C.S
Occupied Cool Mode Start
OC.C.E
Occupied Cool Mode End
TEMP
Ctl.Temp RAT,SPT or ZONE
OC.H.E
Occupied Heat Mode End
OC.H.S
Occupied Heat Mode Start
Unoccup. Heat Mode End
UN.H.E
UN.H.S
Unoccup. Heat Mode Start
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
MODE — RUN STATUS (cont)
EXPANSION
RANGE
UNITS
CCN POINT
0 to 100
%
HMZRCAPC
0 to 100
%
COND_EXV
0 to 100
%
No/Yes
HUM3WVAL
-20 to 140
dF
COOLCPNT
-40 to 240
dF
-20 to 140
dF
HEATCPNT
-40 to 240
dF
0 to 100
%
XV1APOSP
0 to 100
%
XV2APOSP
0 to 100
%
XV1BPOSP
0 to 100
%
XV2BPOSP
-100 to 200
^F
-100 to 200
^F
-100 to 200
^F
-100 to 200
^F
5 to 40
^F
SH_SP_CT
0 to 10
^F
0 to 100
%
0 to 5
EXV_PG_C
0.5 to 60
0 to 100
%
EXCSMP_C
0 to 100
%
VFD1_SPD
0 to 30000
0 to 500
VFD1FREQ
0 to 999
amps
VFD1AMPS
-200 to 200
%
VFD1TORQ
-150 to 150
kW
0 to 1000
voltage
0 to 1000
voltage
VFD1VOUT
0 to 150
VFD1TEMP
0 to 65535
hours
VFD1RUNT
0 to 65535
0 to 65535
0 to 100
%
VFD2_SPD
50 to 30000
10 to 500
VFD2FREQ
0 to 999
amps
VFD2AMPS
-200 to 200
%
VFD2TORQ
-150 to 150
kW
0 to 1000
voltage
0 to 1000
voltage
VFD2VOUT
0 to 150
VFD2TEMP
0 to 65535
hours
VFD2RUNT
0 to 65535
0 to 65535
0 to 100
%
MM_A_VFD
0 to 100
%
MM_B_VFD
0 to 100
dF
UCCLSTRT
0 to 100
dF
UCCL_END
0 to 100
dF
OCCLSTRT
0 to 100
dF
OCCL_END
0 to 100
dF
CTRLTEMP
0 to 100
dF
OCHT_END
0 to 100
dF
OCHTSTRT
0 to 100
dF
UCHT_END
0 to 100
dF
UCHTSTRT
188
WRITE STATUS
BYP_EXV
EDT
LAT
SH_A1
SH_A2
SH_B1
SH_B2
forcible
FL_SP_CT
forcible
COXMP_C
forcible
EXV_TI_C
forcible
forcible
VFD1RPM
VFD1PWR
VFD1VDC
VFD1KWH
VFD1LFC
VFD2RPM
VFD2PWR
VFD2VDC
VFD2KWH
VFD2LFC
PAGE NO.
52,53,118
52,53,118
52,53,118
52,53,118
52,53,118
52,53,118
53,118
53,118
52,118
52,118
52,118
52,118
52,118
52,118
52,118
52,118
52,118,126
52,118
51,111
52,118
52,118
52,118
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
119
51,120
51,120
51,120
51,120
51,120
51,120
51,120
51,120