Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 153

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

POINT NAME
POINT DESCRIPTION
INPUTS
PPS
Plenum Press. Safety Sw.
SACFM
Supply Air CFM
RACFM
Return Air CRM
OUTPUTS
MMV_B
Motor Master VFD B
CMPA1CAP
Compressor A1 Solenoid
HUMIDRLY
Humidifier Relay
SFBYRLY
Supply Fan Bypass Relay
PEBYRLY
PE/Ret. Fan Bypass Relay
Fig. 33 — Economizer Control Board (EXB) and Rooftop Control Board (RXB)
Table 96 — Economizer Control Board (EXB) Inputs and Outputs
Switch Input
Transducer (4-20mA)
Transducer (4-20mA)
4-20mA
Digital
Relay
Relay
Relay
TYPE OF I/O
I/O POINT NAME
153
CONTROL
BOARD
DI1
EXB
AN1
EXB
AN2
EXB
AO1
EXB
PP/MP
EXB
RLY1
EXB
RLY2
EXB
RLY3
EXB
CONNECTOR
PIN NO.
J4, 1-2
J5, 1-3
J5, 4-6
J9, 1-2
J7, 1-3
J8, 1-3
J8, 4-6
J8, 7-9

Advertisement