Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 224

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

TABLE
OCCDEFME
PRESBLDG
PRESDUCT
STAGEGAS
APPENDIX B — CCN TABLES (CONT)
MAINTENANCE DISPLAY TABLES (cont)
DISPLAY NAME
Current Day,Time & Date:
Occupancy Controlled By:
Currently Occupied ?
Current Occupied Time
Current Unoccupied Time
Next Occupied Day & Time
Next Unocc. Day & Time
Last Unocc. Day & Time
Current Occup. Period #
Timed-Override in Effect
Timed-Override Duration
Building Pressure
Return Air CFM
Exhaust Air CFM
Supply Air CFM
Outside Air CFM
Power Exhaust Bypass Rly
Exhaust Fan Commanded %
Building Pressure Setp.
BP Setpoint Offset
Fan Track Learn Enable
Fan Track Learn Rate
Fan Track Initial DCFM
Fan Track Max Clamp
Fan Track Max Correction
Fan Track Internl EEPROM
Fan Track Reset Internal
Fan Track Internal RAM
Fan Track Control D.CFM
Static Pressure
Supply Fan Commanded %
Econ 2 Ret Act Curr Pos
Econ 2 Ret Cmd Position
Static Pressure Setpoint
Static Pressure Reset
Heating Mode...........:
Requested Heat Stage
Heating Control Point
Staged Heat LAT Sum
Staged Heat LAT 1
Staged Heat LAT 2
Staged Heat LAT 3
Staged Gas Limit Sw.Temp
Heat PID Timer
Staged Gas Capacity Calc
Current Running Capacity
Proportional Cap. Change
Derivative Cap. Change
Maximum Heat Stages
Hi Limit Switch Tmp Mode
LAT Cutoff Mode
Capacity Clamp Mode
RANGE
UNITS
24-char ASCII
24-char ASCII
24-char ASCII
24-char ASCII
No/Yes
1-char ASCII
hh:mm
hh:mm
15-char ASCII
15-char ASCII
15-char ASCII
11001100 (flags)
No/Yes
hours
in H2O
CFM
CFM
CFM
CFM
Off/On
%
in H2O
in H2O
No/Yes
mins
CFM
CFM
CFM
CFM
No/Yes
CFM
CFM
in H2O
%
%
%
in H2O
12-char ASCII
degF
degF
degF
degF
degF
degF
secs
%
%
Off/On
Off/On
Off/On
224
POINT NAME
WRITE STATUS
TIMEDATE
OCDFTXT1
OCDFTXT2
OCDFTXT3
MODE_OCC
STRTTIME
ENDTIME
NXTOC_DT
NXTUN_DT
PRVUN_DT
PER_NO
OVERLAST
OVR_HRS
BP
forcible
RACFM
EACFM
SACFM
OACFM
PEBYRLY
EFAN_VFD
BPSP
config
BPSO
config
DCFM_CFG
config
DCFMRATE
config
DCFMSTRT
config
DCFM_MAX
config
DCFM_ADJ
config
DCFM_OFF
config
DCFMRSET
DCFM_RAM
DELTACFM
SP
forcible
SFAN_VFD
ECN2RPOS
ECN2CPOS
forcible
SPSP
config
SPRESET
forcible
HT_STAGE
HEATCPNT
LAT_SGAS
LAT1SGAS
LAT2SGAS
LAT3SGAS
LIMSWTMP
HTSGTIMR
HTSGCALC
HTSG_CAP
HTSG_P
HTSG_D
HTMAXSTG
LIMTMODE
LATCMODE
CAPMODE

Advertisement

Table of Contents
loading

Table of Contents