ITEM
TEST
Service Test Mode
STOP
Local Machine Disable
S.STP
Soft Stop Request
FAN.F
Supply Fan Request
INDP
TEST INDEPENDENT OUTPUTS
HUM.R
Humidifier Relay
ALRM
Remote Alarm/Aux Relay
FANS
TEST FANS
F.MOD
Fan Test Automatic?
E.POS
Econ 1 Out Act. Cmd. Pos.
SF.BY
Supply Fan Bypass Relay
S.VFD
Supply Fan Commanded %
PE.BY
Power Exhaust Bypass Relay
E.VFD
Exhaust Fan Commanded %
A.VFD
MtrMaster A Commanded %
B.VFD
MtrMaster B Commanded %
CDF.1
Condenser Fan Output 1
CDF.2
Condenser Fan Output 2
CDF.3
Condenser Fan Output 3
CDF.4
Condenser Fan Output 4
CDF.5
Condenser Fan Output 5
AC.T.C
CALIBRATE TEST-ACTUATORS
EC1.C
Econ 1 Out Act.Cmd.Pos.
E1.CL
Economizer Calibrate Cmd
E1C.A
Econ 1 Out Act Ctl Angle
EC2.C
Econ 2 Ret Act.Cmd.Pos.
E2.CL
Economzr 2 Calibrate Cmd
E2C.A
Econ 2 Ret Act Ctl Angle
EC3.C
Econ 3 Out Act. Cmd.Pos.
E3.CL
Economzr 3 Calibrate Cmd
E3C.A
Humidifier Act. Ctrl. Ang.
HTC.C
Ht.Coil Command Position
HT.CL
Heating Coil Act. Cal.Cmd
HTC.A
Heat Coil Act.Ctl.Angle
HMD.C
Humidifier Command Pos.
HM.CL
Humidifier Act. Cal.Cmd
HMD.A
Humidifier Act.Ctrl.Ang.
HTC.3
Ht.Coil Command Position
HC.3L
Heat Coil Act 3 Cal Cmd
HC3.A
Heat Coil Act 3 Cal Cmd
HTC.4
Ht.Coil Command Position
HC.4L
Heat Coil Act 4 Cal Cmd
HC4.A
HTC4 Control Angle
SRCH
SEARCH FOR SERIAL NUMBER
ACTV
Belimo Serial Num Search
ECN.1
Economizer 1 Search
ECN.2
Economizer 2 Search
ECN.3
Economizer 3 Search
HT.CL
Heat Coil Valve Search
HUMD
Humidifier Valve Search
HT.C3
Heat Coil 3 Valve Search
HT.C4
Heat Coil 4 Valve Search
HMZR
TEST HUMIDIMIZER
RHV
Humidimizer 3-Way Valve
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
C.CAL
Condenser EXV Calibrate
B.CAL
Bypass EXV Calibrate
EXVS
TEST CIRCUIT EXVS
A1.EX
Circuit A EXV 1 Position
A2.EX
Circuit A EXV 2 Position
B1.EX
Circuit B EXV 1 Position
Table 23 — Service Test
EXPANSION
RANGE
UNITS
Off/On
No/Yes
No/Yes
No/Yes
Off/On
Off/On
No/Yes
0-100
Off/On
0-100
%
Off/On
0-100
%
0-100
%
0-100
%
Off/On
Off/On
Off/On
Off/On
Off/On
0-100
%
No/Yes
0-100
0-100
%
No/Yes
0-100
0-100
%
No/Yes
0-100
0-100
%
No/Yes
0-100
0-100
%
No/Yes
0-100
0-100
No/Yes
0-100
0-100
No/Yes
0-100
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
Off/On
0-100
%
0-100
%
Off/On
Off/On
0-100
%
0-100
%
0-100
%
30
CCN POINT
WRITE STATUS
MAN_CTRL
UNITSTOP
SOFTSTOP
SFANFORC
HUMR_TST
ALRM_TST
FANAUTO
ECONFANS
SFAN_TST
SFVFDTST
PEBY_TST
EFVFDTST
OAVFDTST
OBVFDTST
CDF1_TST
CDF2_TST
CDF3_TST
CDF4_TST
CDF5_TST
ECON1TST
ECONOCAL
CONCANG
ECON2TST
ECON2CAL
ECN2CANG
ECON2TST
ECON3 CAL
HUMDCANG
HTCLACTC
HCOILCAL
HTCLCANG
HUMD_TST
HUMIDCAL
HUMDCANG
HTC3ACTS
HTC3_CAL
HTC3CANG
HTC4ACTS
HTC4_CAL
HTC4CANG
BELSERCH
EC1SERCH
EC2SERCH
EC3SERCH
HTCSERCH
UMSERCH
HTC3SRCH
HTC4SRCH
RHVH_TST
CEXVHTST
BEXVHTST
CEXV_CAL
BEXV_CAL
A_X1_TST
A_X2_TST
B_X1_TST