Carrier FX4D Product Data

Carrier FX4D Product Data

Comfort fx4d series fan coil sizes 019 thru 061

Advertisement

FX4D
Comfortt Series Fan Coil
Sizes 019 thru 061
Product Data
The FX4D fan coils combine the proven technology of Carrier fan
coil units with Puron®, the environmentally sound refrigerant.
These fan coils are loaded with popular features. Factory- -installed,
refrigerant- -specific thermostatic expansion valves (TXV) are
standard with these fan coil designs. The designs feature contoured
condensate pans with rugged, drain connections, ensuring that little
water is left in the unit at the end of the cooling duty cycle. The
lack of standing condensate and corrosion free pans improves IAQ
and product life, features homeowners appreciate.
Standard features include grooved copper tubing and louvered
aluminum fins. The large face areas of the refrigerant coils provide
superior efficiency for high SEER and HSPF performance. Coil
circuiting has also been updated to make the most of all Carrier
heat pumps and air conditioners. Also units come with solid state
fan controls, 1- -in (25mm) thick insulation with R- -value of 4.2,
multi- -speed motors, and fully- -wettable coils. Units can
accommodate factory- - and/or field- -installed heaters from 3 to 30
kW.
It also should be noted that the unique cabinet design of these fan
coils meet new stringent regulations for cabinet air leakage - - a
requirement of 2% cabinet leakage rate when tested at 1.0 inches of
static pressure.
The FX4D fan coil is the Puron® refrigeration design loaded with
popular features. It comes in a pre- -painted (taupe metallic)
galvanized steel casing and is shipped with a cleanable, permanent
framed filter, and a factory- -supplied power plug. ArmorCoatt
provides a tin plating of the indoor coil's copper hairpins. This
creates a barrier between the corrosion- -causing elements and the
coil. These fan coils utilize the latest in electronic commutation
motor (ECM) technology through the use of high efficiency, X13,
blower motors.
A10009
AIR HANDLER TECHNOLOGY
AT ITS FINEST

Advertisement

Table of Contents
loading

Summary of Contents for Carrier FX4D

  • Page 1 Product Data AIR HANDLER TECHNOLOGY AT ITS FINEST The FX4D fan coils combine the proven technology of Carrier fan coil units with Puron®, the environmentally sound refrigerant. These fan coils are loaded with popular features. Factory- -installed, refrigerant- -specific thermostatic expansion valves (TXV) are standard with these fan coil designs.
  • Page 2: Standard Features

    S Leak- -preventing sweat connections S Modular cabinets available on 037 through 061 sizes. S Designed for manufactured housing applications. ADDITIONAL FEATURES FX4D S Puron®, environmentally sound refrigerant S Factory- -installed Puron® refrigerant thermostatic expansion valves (TXV) S Factory- -installed heater packages available...
  • Page 3: Model Number Nomenclature

    MODEL NUMBER NOMENCLATURE CARRIER FAN COILS Product Type Heating Size Fan Coil, Multipoise with Puron 000 = No Heat 005 = 5kW Electrical 008 = 8 kW N - - 208/230v, 1 ph, 60 Hz 010 = 10kW 015 = 15kW...
  • Page 4: Dimensions

    CONNECTION LOCATIONS SHOWN DOWNFLOW OR HORIZ. FOR UPFLOW OR HORIZ. RIGHT APPLICATIONS LEFT APPLICATIONS FRONT VIEW SHOWN WITH "A" COIL DETAILS CONNECTION "A" COILS LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS DOWNFLOW APPLICATIONS A10032 Fig. 1 - - FX4D - - English...
  • Page 5 2 11/16" 5 7/8" 4 3/4" 2 3/16" DOWNFLOW 1 3/16" 1/2" TYP. 7 7/8" TYP.* (FIELD CONVERTED) (2 PLACES)* 1 13/16" UPFLOW TYP. 7/8" HORIZ. RIGHT TYP.* (AS SHIPPED) (FIELD CONVERTED) A10033 Fig. 2 - - FX4D - - English...
  • Page 6 INLET AIR DOWNFLOW OR HORIZ. FOR UPFLOW OR HORIZ. RIGHT APPLICATIONS LEFT APPLICATIONS FRONT VIEW "A" COILS SHOWN WITH "A" COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS DOWNFLOW APPLICATIONS A10034 Fig. 3 - - FX4D - - Metric...
  • Page 7 11.1 TYP, (4 PLACES)* 38.1 77.8 68.3 120.6 DOWNFLOW 55.6 TYP. 149.2 (FIELD CONVERTED) (2 PLACES)* 30.2 12.7 200.0 TYP.* UPFLOW 46.0 (AS SHIPPED) TYP. 22.2 HORIZ. RIGHT TYP.* (FIELD CONVERTED) A10035 Fig. 4 - - FX4D - - Metric...
  • Page 8: Physical Data

    6th digit: B --- Modular cabinet, F --- Single piece cabinet 10th digit: 0 --- Standard copper coil, T --- ArmorCoatt SPECIFICATIONS MODEL FX4D COIL Puronr Refrigerant TXV --- factory installed hard --- shutoff, bi--- flow type for heat pump application...
  • Page 9: Airflow Performance

    AIRFLOW PERFORMANCE (CFM) MODEL & BLOWER 0.10 0.20 0.30 0.40 0.50 0.60 SIZE SPEED Tap 5 Tap 4 FX4D 019 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 FX4D 025 Tap 3 Tap 2 Tap 1 Tap 5 1189 1151...
  • Page 10: Gross Cooling Capacities

    0.02 0.02 0.02 62 / 17 0.02 0.02 0.02 0.07 0.24 72 / 22 0.00 0.00 0.00 0.01 0.02 FX4D 67 / 19 0.02 0.02 0.02 0.02 0.03 62 / 17 0.02 0.02 0.03 0.08 0.25 72 / 22 0.00 0.00...
  • Page 11 PERFORMANCE DATA (cont) CFM --- Cubic Ft per Minute EWB --- Entering Wet Bulb _F (_C) LWB --- Leaving Wet Bulb _F (_C) TC --- Gross Cooling Capacity 1000 Btuh SHC --- Gross Sensible Capacity 1000 BF --- Bypass Factor MBH --- 1000 Btuh Btuh NOTES:...
  • Page 12 PERFORMANCE DATA (cont) FACTORY- -INSTALLED FILTER STATIC PRESSURE DROP (in wc) UNIT SIZE FX4D 1000 1200 1400 1600 1800 2000 019, 025 0.012 0.022 0.048 0.072 031, 037, 043 0.036 0.051 0.07 0.092 0.12 049, 061 0.073 0.086 0.105 0.13...
  • Page 13: Electrical Data

    ELECTRICAL DATA FOR UNITS WITH FACTORY- -INSTALLED HEAT SINGLE CIRCUIT DUAL CIRCUIT HEAT PACK Htr. Htr. FX4DNF VOLTS/PH/ MOCP MOCP INSTALLED Heater Amps Amps MODEL NO. MOCP MKFCEH Amps L1/L2 L1/L2 L1/L2 L3/L4 L3/L4 L3/L4 019005 2.8 208/230/1/60 0501N05 18.1/20.0 26.1/28.5 30/30 025005 2.8 208/230/1/60 0501N05...
  • Page 15: Heater Electrical Data

    HEATER ELECTRICAL DATA FACTORY- -INSTALLED HEATER OPTIONS* MODEL FX4DNF 10, 15 For field---installed heater/fan coil combinations, see Accessory Electric Heaters. ELECTRIC HEATER INTERNAL PROTECTION FUSE CKT BKR* HEATER kW PHASE QTY/SIZE QTY/SIZE — 1/60 — 1/60 — — — 1/60 2/30–2/60 2/60 —...
  • Page 16: Accessory Kits

    The AIRA electronic air cleaner comes ready for 115- -v operation. REQUIRED USE: This kit is required when running 240- -volt circuit to air cleaner. Catalog No: FX4D---01PD Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/10 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents