Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 59

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

MM
7
9
8
A1
A2
4
5
6
A3
A4
MM
1
3
2
POWER
BOX
Controlling Output
Contactor
Circuit
Software
Board
Conrolled
A
CONDFAN1
MBB Rly 6
OFC1
Common
CONDFAN2
MBB Rly 5
OFC2
B
CONDFAN3
RCB Rly 1
OFC3
A
CONDFAN4
RCB Rly 2
OFC4
B
CONDFAN5
RCB Rly 3
OFC5
Common,
M.M.=YES
or NO
Contactor
Software Pts
# of Fans ON
Stage 1A OFC1
CONDFAN1
1
Stage 1B OFC3
CONDFAN3
1
Stage 2A OFC2
CONDFAN2
3
Stage 2B OFC2
CONDFAN2
3
Stage 3A OFC1,2
CONDFAN1,2
4
Stage 3B OFC2,3
CONDFAN2,3
4
Stage 4A OFC2,4
CONDFAN2,4
5
Stage 4B OFC2,5
CONDFAN2,5
5
Stage 5A OFC2,1,4
CONDFAN1,2,4
6
Stage 5B OFC2,5,3
CONDFAN2,3,5
6
LEGEND
MM
— Motormaster
®
Control
OFC
— Outdoor Fan Contactor
OFM
— Outdoor Fan Motor
Fig. 8 — 90 to 130-Ton High Efficiency and 130 and 150-Ton Standard Efficiency Unit Condenser Fan Staging Sequence
Circuit B
Coils
B4
B3
B2
B1
Circuit A
Coils
OFM(s)
Logic
Controlled
See Table
OFM2
See Table
OFM 4,5,6
See Table
OFM8
OFM 1,3
See Table
OFM 7,9
See Table
Fans ON
Ckt A # Fans ON Ckt B # Fans ON
Ckt A on. Stage up when either circuit is > SCT_MAX Stage up to Stage 2A AND Stage 2B when either circuit SCT>SCT_MAX
OFM2
1
0
Ckt B on. Stage up when either circuit is > SCT_MAX Stage up to Stage 2A AND Stage 2B when either circuit SCT>SCT_MAX
OFM8
0
1
OFM4,5,6
1.5
1.5
Stage up by individual circuit when SCT > SCT_MAX
Stage down when both circuits SCT < SCT_MIN
OFM4,5,6
1.5
1.5
OFM4,5,6,2
2.5
1.5
Stage up & down by individual circuit
OFM4,5,6,8
1.5
2.5
Up if SCT > SCT_MAX, Down if SCT<SCT_MIN
OFM4,5,6,1,3
3.5
1.5
Stage up & down by individual circuit
OFM4,5,6,7,9
1.5
3.5
Up if SCT > SCT_MAX, Down if SCT<SCT_MIN
OFM4,5,6,1,2,3
4.5
1.5
Stage down by individual circuit
OFM4,5,6,7,9,8
1.5
4.5
Down if SCT<SCT_MIN
Applicable Units
Tonnage
Efficiency
90
High
105
High
120
High
130
Standard
130
High
150
Standard
Staging Logic
Stage up to Stage 3A when SCTA>SCT_MAX
Stage up to Stage 3B when SCTB>SCT_MAX
Stage up to Stage 4A when SCTA>SCT_MAX
Stage up to Stage 4B when SCTB>SCT_MAX
Stage up to Stage 5A when SCTA>SCT_MAX
Stage up to Stage 5B when SCTB>SCT_MAX
Stage Up Logic
Stage down, OFC1 off, when Ckt A is off.
Stage down, OFC3 off, when Ckt B is off.
Stage down to Stage 1A when SCTA AND SCTB < SCT_MIN
Stage down to Stage 1B when SCTA AND SCTB < SCT_MIN
Stage down to Stage 2A when SCTA<SCT_MIN
Stage down to Stage 2B when SCTB<SCT_MIN
Stage down to Stage 3A when SCTA<SCT_MIN
Stage down to Stage 3B when SCTB<SCT_MIN
Stage down to Stage 4A when SCTA<SCT_MIN
Stage down to Stage 4B when SCTB<SCT_MIN
Stage Down Logic