Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 122

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ALARM OR
ALERT
NUMBER
T093
Circ B Suction Press Transducer Failure
T094
Circ A EXV 1 Thermistor Failure
T095
Circ A EXV 2 Thermistor Failure
T096
Circ B EXV 1 Thermistor Failure
T097
Circ B EXV 2 Thermistor Failure
T098
Circuit A Liquid Temperature Thermistor Failure
T099
Circuit B Liquid Temperature Thermistor Failure
T100
Circ A Liquid Press Transducer Failure
T101
Circ B Liquid Press Transducer Failure
T110
Circuit A Loss of Charge
T111
Circuit B Loss of Charge
T112
Low Circuit A Charge Detected
T113
Low Circuit B Charge Detected
T114
High Circuit A Charge Detected
T115
High Circuit B Charge Detected
P120
Circuit A Low Saturated Suction Temp, Comp Shutdown
T120
Circuit A Low Saturated Suction Temperature Alert
A120
Circuit A Low Saturated Suction Temperature Alarm
P121
Circuit B Low Saturated Suction Temp, Comp Shutdown
T121
Circuit B Low Saturated Suction Temperature Alert
A121
Circuit B Low Saturated Suction Temperature Alarm
T122
Circuit A High Saturated Suction Temperature
T123
Circuit B High Saturated Suction Temperature
P126
Circuit A High Head Pressure, Comp Shutdown
T126
Circuit A High Head Pressure Alert
A126
Circuit A High Head Pressure Alarm
P127
Circuit B High Head Pressure, Comp Shutdown
T127
Circuit B High Head Pressure Alert
A127
Circuit B High Head Pressure Alarm
T128
Digital Scroll A1 High Discharge Temperature Alert
A128
Digital Scroll A1 High Discharge Temperature Alarm
A140
Reverse Rotation Detected
A150
Unit is in Emergency Stop
A152
Unit Down due to Failure
T153
Real Time Clock Hardware Failure
A154
Serial EEPROM Hardware Failure
T155
Serial EEPROM Storage Failure Error
A156
Critical Serial EEPROM Storage Fail Error
A157
A/D Hardware Failure
A169
EXV Board Communication Failure
T170
Loss of Communication with the Compressor Expansion Module
A171
Staged Gas Control Board Comm Failure
T172
Control Expansion Module Comm Failure
A173
RXB board Communication Failure
A174
EXB board Communication Failure
A175
VFD1 Communication Failure
T176
VFD2 Communication Failure
T177
4-20 mA Demand Limit Failure
T178
4-20 mA Static Pressure Reset Fail
A179
Cir. A EXV Board Communication Failure
A180
Cir. B EXV Board Communication Failure
T181
Loss of Communication with Outside Air Limit
A200
Linkage Timeout Error - Comm Failure
T210
Building Pressure Transducer Failure
T211
Static Pressure Transducer Failure
T220
Indoor Air Quality Sensor Failure
T221
Outdoor Air Quality Sensor Failure
T229
Economizer Min Pos Override Input Failure
T245
Outside Air CFM Sensor Failure
T246
Supply Air CFM Sensor Failure
T247
Return Air CFM Sensor Failure
T248
Exhaust Air CFM Sensor Failure
T300
Space Temperature Below Limit
T301
Space Temperature Above Limit
T302
Supply Temperature Below Limit
T303
Supply Temperature Above Limit
T304
Return Temperature Below Limit
T305
Return Temperature Above Limit
Table 92 — Alert and Alarm Codes (cont)
DESCRIPTION
ACTION TAKEN BY CONTROL
Circuit shut down
Circuit shut down
Circuit shut down
Circuit shut down
Circuit shut down
Alert Only - no circuit prognostics
Alert Only - no circuit prognostics
Alert Only - no circuit prognostics
Alert Only - no circuit prognostics
Circuit locked off
Circuit locked off
Alert Only
Alert Only
Alert Only
Alert Only
Circuit staged down
Circuit shut down
Circuit locked off
Circuit staged down
Circuit shut down
Circuit locked off
Alert Only
Alert Only
Circuit stage down
Circuit shut down
Circuit locked off
Circuit stage down
Circuit shut down
Circuit locked off
Digital compressor A1 shutdown
Digital compressor A1 locked off
Stop unit
Unit shut down
No mechanical cooling available
Unit shut down
Unit shut down
Alert only
Unit shut down
Unit shut down
Humidimizer control disabled
Compressors A3, A4, B3 and B4 disabled
Staged gas control disabled
All CEM board functions disabled
Unit shut down
All EXB board functions disabled
Unit shut down
No building pressure control
No demand limiting
No static pressure reset
Circuit shut down
Circuit shut down
Alert only
Resorts to local unit set points
No building pressure control function
No static pressure control
No IAQ control
OAQ defaults to 400 ppm
Operate without override
No OA CFM control
Unit shut down
Unit shut down
Alert only
Alert only
Alert only
Alert only
Alert only
Alert only
Alert only
122
RESET METHOD
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Automatic
Automatic
Manual
Manual
Manual
Automatic
Automatic
Manual
Automatic
Automatic
Manual
Automatic
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic