ITEM
COOL
COOLING CONFIGURATION
A1.EN
Enable Compressor A1
A2.EN
Enable Compressor A2
A3.EN
Enable Compressor A3
A4.EN
Enable Compressor A4
B1.EN
Enable Compressor B1
B2.EN
Enable Compressor B2
B3.EN
Enable Compressor B3
B4.EN
Enable Compressor B4
CS.A1
CSB A1 Feedback Alarm
CS.A2
CSB A2 Feedback Alarm
CS.A3
CSB A3 Feedback Alarm
CS.A4
CSB A4 Feedback Alarm
CS.B1
CSB B1 Feedback Alarm
CS.B2
CSB B2 Feedback Alarm
CS.B3
CSB B3 Feedback Alarm
CS.B4
CSB B4 Feedback Alarm
Z.GN
Capacity Threshold Adjust
DT.GN
SUMZ EDT Derivative Gain
MC.LO
Compressor Lockout Temp
LLAG
Lead/Lag Operation ?
HC.EV
High Capacity Evaporator
H.ODF
High Efficiency OD Fans?
M.M.
Motor Master Control ?
MM.OF
MM Setpoint Offset
M.PID
MOTORMAST PID CONFIGS
MM.RR
Motor Master PI Run Rate
MM.PG
Motor Master Prop Gain
MM.PD
Motor Master Deriv. Gain
MM.TI
Motor Master Integ. Time
SCT.H
Maximum Condenser Temp
SCT.L
Minimum Condenser Temp
DG.A1
A1 is Digital Scroll
MC.A1
A1 Min Digital Capacity
DS.AP
Dig Scroll Adjust Delta
DS.AD
Dig Scroll Adjust Delay
DS.RP
Dig Scroll Reduce Delta
DS.RD
Dig Scroll Reduce Delay
DS.RO
Dig Scroll Reduction OAT
DS.MO
Dig Scroll Max Only OAT
MLV
Min Load Valve Enable
H.SST
Hi SST Alert Delay Time
RR.VF
Rev Rotation Verified?
CS.HP
Use CSBs for HPS Detect?
EXV.C
EXV CIRCUIT CONFIGS
EX.SA
Cir. EXV Start Algorithm
SH.SP
EXV Superheat Setpoint
SH.DB
EXV Superheat Deadband
MOP.S
Max Oper. Pressure SP
CS.DE
EXV Cir Start Delay Secs
CS.PD
EXV Cir PreMove Dly Secs
EX.MN
Comp. Cir. Exv. Min Pos%
EX.MC
Comp Cir EXV Mn Strt Pos
EN.SC
Enab Cir Shtdwn w/ flood
FL.TM
Flooding Detect Time
E.PID
EXV PID CONFIGS
EX.RR
EXV PID Run Rate
EX.PG
EXV PID Prop. Gain
EX.TI
EXV Integration Time
EX.HO
High OAT Lim (EXV Gain)
EX.LO
Low OAT Lim (EXVGain)
EX.FG
%EXV Move on Cir. Stg Up
EX.FD
%EXV Move on Cir. Stg Dw
EX.CF
EXV Pre-Move Config
EX.PM
EXV Pre-Move Delay Secs
FL.SP
EXV SH Flooding Setpoint
FL.OC
Flood Ovrde Press Cutoff
FL.OD
Flooding Override Delay
Table 28 — Cooling Configuration
EXPANSION
RANGE
UNITS
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
0.1 to 10
0.1 to 3
–25 to 55
dF
0 to 2
No/Yes
No/Yes
No/Yes
–20 to 20
dF
5 to120
0 to 5
sec
0 to 5
0.5 to 50
100 to 150
dF
40 to 90
dF
No/Yes
30 to 100
%
0 to 100
%
15 to 60
sec
0 to 100
%
15 to 60
sec
70 to 120
dF
70 to 120
dF
Disable/Enable
5 to 30
min
No/Yes
No/Yes
0 to 1
5 to 40
dF
0 to 2
dF
40 to 120
dF
10 to 240
sec
0 to 30
sec
0 to 100
%
0 to 100
%
No/Yes
15 to 900
5 to 120
sec
0 to 5
0.5 to 60
50 to 95
dF
40 to 80
dF
0 to 100
%
0 to 100
%
0 to 3
sec
0 to 30
sec
0 to 10
dF
0 to 1000
psig
0 to 255
sec
48
CCN POINT
DEFAULT
CMPA1ENA
Enable
CMPA2ENA
Enable
CMPA3ENA
Enable
CMPA4ENA
Enable
CMPB1ENA
Enable
CMPB2ENA
Enable
CMPB3ENA
Enable
CMPB4ENA
Enable
CSB_A1EN
Enable
CSB_A2EN
Enable
CSB_A3EN
Enable
CSB_A4EN
Enable
CSB_B1EN
Enable
CSB_B2EN
Enable
CSB_B3EN
Enable
CSB_B4EN
Enable
Z_GAIN
1.0
DTGAIN
1.5
OATLCOMP
53
LLENABLE
0
HCAPEVAP
No
HIGH_EFF
No
MOTRMAST
No
MMSPOFST
-10.0
MM_RATE
5
MINCAPA1
50
MM_DG
0.3
MM_TI
30.0
SCT_MAX
115
SCT_MIN
80
DIGCMPA1
No
MINCAPA1
50
DSADJPCT
100
DSADJDLY
20
DSREDPCT
6
DSREDDLY
30
DSREDOAT
95
DSMAXOAT
105
MLV_ENAB
Disable
HSSTTIME
10
REVR_VER
No
CSBHPDET
Yes
EXV_STAL
0
SH_SP
12.0
SH_DB
0.5
MOP_SP
70
EXVCSDLY
240
EXVCPDLY
30
CC_XMPOS
20.0
EXV_CSMP
30
FL_ENCSD
Yes
FL_DETTM
120
EXV_RATE
5
EXV_PG
0.5
EXV_TI
50
HIGHOAT
70
LOWOAT
60
EXV_FF_G
10
EXV_FF_D
15.0
EXVPMCFG
1
EXVPMDLY
10
FL_SP
6.0
FL_ODPC
600.0
FL_OD
0