Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 203

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
CCN (cont)
CCN CONFIGURATION (cont)
SC.OV (cont)
CCN SCHEDULES-OVERRIDES (cont)
OV.EX
Override Time Limit
SPT.O
SPT Override Enabled ?
T58.O
T58 Override Enabled ?
GL.OV
Global Sched. Override ?
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ
SP.H.O
SPT hi alert limit/occ
SP.L.U
SPT lo alert limit/unocc
SP.H.U
SPT hi alert limit/unocc
SA.L.O
EDT lo alert limit/occ
SA.H.O
EDT hi alert limit/occ
SA.L.U
EDT lo alert limit/unocc
SA.H.U
EDT hi alert limit/unocc
RA.L.O
RAT lo alert limit/occ
RA.H.O
RAT hi alert limit/occ
RA.L.U
RAT lo alert limit/unocc
RA.H.U
RAT hi alert limit/unocc
OAT.L
OAT low alert limit
OAT.H
OAT high alert limit
R.RH.L
RARH low alert limit
R.RH.H
RARH high alert limit
O.RH.L
OARH low alert limit
O.RH.H
OARH high alert limit
SP.L
SP low alert limit
SP.H
SP high alert limit
BP.L
BP low alert limit
BP.H
BP high alert limit
IAQ.H
IAQ high alert limit
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim
RAT.T
RAT Trim
OAT.T
OAT Trim
SPT.T
SPT Trim
L.SW.T
Limit Switch Trim
CCT.T
Air Tmp Lvg Evap Trim
DTA.1
A1 Discharge Temp Trim
SP.A.T
Suct.Press.Circ.A Trim
SP.B.T
Suct.Press.Circ.B Trim
DP.A.T
Dis.Press.Circ.A Trim
DP.B.T
Dis.Press.Circ.B Trim
LP.A.T
Lqd.Press.Circ.A Trim
LP.B.T
Lqd.Press.Circ.B Trim
SW.LG
SWITCH LOGIC:NO / NC
PWS.L
Power Fault Input - Good
MFT.L
Filter Status Inpt-Clean
PFT.L
Post Filter Stat. In-Cln
IGC.L
IGC Feedback - Off
RMI.L
RemSw Off-Unoc-Strt-NoOv
ENT.L
Enthalpy Input - Low
SFS.L
Fan Status Sw. - Off
DL1.L
Dmd.Lmt.Sw.1 - Off
DL2.L
Dmd.Lmt.Sw.2 - Off
IAQ.L
IAQ Disc.Input - Low
FSD.L
Fire Shutdown - Off
PRS.L
Press. Switch - Off
EVC.L
Evacuation Sw. - Off
PRG.L
Smoke Purge Sw. - Off
DH.LG
Dehumidify Sw. - Off
SFB.L
SF Bypass Sw. - Off
PEB.L
PE Bypass Sw. - Off
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
METR
Metric Display
LANG
Language Selection
PAS.E
Password Enable
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION (cont)
EXPANSION
Disable/Enable
RANGE
UNITS
CCN POINT
0 to 4
Hours
No/Yes
No/Yes
No/Yes
GLBLOVER
-10 to 245
dF
-10 to 245
dF
-10 to 245
dF
-10 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
-40 to 245
dF
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 5
"H20
0 to 5
"H20
-0.25 to 0.25
"H20
-0.25 to 0.25
"H20
0 to 5000
-10 to 10
^F
-10 to 10
^F
-10 to 10
^F
-10 to 10
^F
-10 to 10
^F
-10 to 10
^F
-10 to 10
^F
-50 to 50
^F
-50 to 50
PSIG
-50 to 50
PSIG
-50 to 50
PSIG
-50 to 50
PSIG
-50 to 50
PSIG
Open/Close
PWRFLOGC
Open/Close
Open/Close
Open/Close
GASFANLG
Open/Close
Open/Close
ENTHLOGC
Open/Close
Open/Close
DMD_SW1L
Open/Close
DMD_SW2L
Open/Close
Open/Close
Open/Close
PRESLOGC
Open/Close
EVACLOGC
Open/Close
PURGLOGC
Open/Close
Open/Close
SFBYLOGC
Open/Close
PEBYLOGC
Off/On
Off/On
0 to 0
LANGUAGE
203
DEFAULT
OVR_EXT
0
SPT_OVER
Yes
T58_OVER
Yes
No
SPLO
60
SPHO
85
SPLU
45
SPHU
100
SALO
40
SAHO
100
SALU
40
SAHU
100
RALO
60
RAHO
90
RALU
40
RAHU
100
OATL
-40
OATH
150
RRHL
0
RRHH
100
ORHL
0
ORHH
100
SPL
0
SPH
2
BPL
-0.25
BPH
0.25
IAQH
1200
SAT_TRIM
0
RAT_TRIM
0
OAT_TRIM
0
SPT_TRIM
0
LSW_TRIM
0
CCT_TRIM
0
DTA1TRIM
0
SPA_TRIM
0
SPB_TRIM
0
DPA_TRIM
0
DPB_TRIM
0
LPA_TRIM
0
LPB_TRIM
0
Close
FLTSLOGC
Open
PFLTSLGC
Open
Open
RMTINLOG
Open
Close
SFSLOGIC
Open
Open
Open
IAQINLOG
Open
FSDLOGIC
Open
Open
Open
Open
DHDISCLG
Open
Open
Open
DISPTEST
Off
DISPUNIT
Off
0
PASS_EBL
Enable
PAGE NO.
94,95
94,95
94,95
94,95
94,96,130
94,96,130
94,96,130
94,96,130
95,96,130
95,130
95,130
95,130
95,130
95,130
95,130
95,130
95,131
95,131
95,130
95,130
95,96
95,96
95,96,130
95,96,130
96,130
95,96,130
96,131
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
96,97
98
96,98
98
98
37,98,100
98
98
37,98
37,98
37,98
37,98
98
98
98
98
98
98
98,99
98,99
98,99
98,99

Advertisement

Table of Contents
loading

Table of Contents