Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 117

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
ECON
ECONOMIZER RUN STATUS
EC1.P
Economzr1 Act.Curr.Pos.
EC2.P
Economzr2 Act.Curr.Pos.
EC3.P
Economzr3 Act.Curr.Pos.
ECN.C
Economizer Act.Cmd.Pos.
ACTV
Economizer Active?
SACA
Single Act CFM Ctl Activ
DISA
ECON DISABLING CONDITIONS
UNV.1
Econ1 Act. Unavailable?
UNV.2
Econ2 Act. Unavailable?
UNV.2
Econ3 Act. Unavailable?
ENTH
Enth. Switch Read High?
DBC
DBC - OAT Lockout?
DEW
DEW - OA Dewpt.Lockout?
DDBC
DDBD- OAT > RAT Lockout?
OAEC
OAEC- OA Enth Lockout?
DEC
DEC - Diff.Enth.Lockout?
EDT
EDT Sensor Bad?
OAT
OAT Sensor Bad?
FORC
Economizer Forced?
SFON
Supply Fan Not On 30s?
CLOF
Cool Mode Not In Effect?
OAQL
OAQ Lockout in Effect?
HELD
Econ Recovery Hold Off?
DH.DS
Dehumid. Disabled Econ.?
O.AIR
OUTSIDE AIR INFORMATION
OAT
Outside Air Temperature
OA.RH
Outside Air Rel. Humidity
OA.E
Outside Air Enthalpy
OA.D.T
Outside Air Dewpoint Temp
COOLING INFORMATION
The Cooling Information run status display table provides in-
formation on the cooling operation and the Humidi-MiZer
operation of the unit. See Table 85.
Current Running Capacity (C.CAP)
This variable represents the amount of capacity currently run-
ning as a percent.
Current Cool Stage (CUR.S)
This variable represents the cool stage currently running.
Requested Cool Stage (REQ.S)
This variable represents the requested cool stage. Cooling relay
timeguards in place may prevent the requested cool stage from
matching the current cool stage.
Maximum Cool Stages (MAX.S)
This variable is the maximum number of cooling stages the
control is configured for and capable of controlling.
Active Demand Limit (DEM.L)
If demand limit is active, this variable will represent the
amount of capacity that the control is currently limited to.
Capacity Load Factor (SMZ)
This factor builds up or down over time (–100 to +100) and is
used as the means of adding or subtracting a cooling stage
during run time. It is a normalized representation of the rela-
tionship between "Sum" and "Z." See the SUMZ Cooling Al-
gorithm section on page 51.
Next Stage EDT Decrease (ADD.R)
This variable represents (if adding a stage of cooling) how much
the temperature should drop in degrees depending on the R.PCT
calculation and how much additional capacity is to be added.
Table 84 — Economizer Run Status Display Table
EXPANSION
®
RANGE
UNITS
0-100
%
0-100
%
0-100
%
0-100
%
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
–40-240
dF
0-100
%
–20-10000
–40-240
dF
ADD.R = R.PCT * (C.CAP – capacity after adding a cooling
stage)
For example: If R.PCT = 0.2 and the control would be adding
20% cooling capacity by taking the next step up,
0.2 times 20 = 4°F ADD.R
Next Stage EDT Increase (SUB.R)
This variable represents (if subtracting a stage of cooling) how
much the temperature should rise in degrees depending on the
R.PCT calculation and how much capacity is to be subtracted.
SUB.R = R.PCT * (C.CAP – capacity after subtracting a cool-
ing stage)
For example: If R.PCT = 0.2 and the control would be sub-
tracting 30% capacity by taking the next step down,
0.2 times –30 = –6°F SUB.R.
Rise Per Percent Capacity (R.PCT)
This is a real-time calculation that represents the amount of de-
grees of drop/rise across the evaporator coil versus percent of
current running capacity.
R.PCT = (MAT – EDT)/C.CAP
Cap Deadband Subtracting (Y.MIN)
This is a control variable used for Low Temp Override
(L.TMP) and Slow Change Override (SLOW).
Y.MIN = –SUB.R*0.4375
Cap Deadband Adding (Y.PLU)
This is a control variable used for High Temp Override
(H.TMP) and Slow Change Override (SLOW).
Y.PLU = –ADD.R*0.4375
117
CCN POINT
WRITE STATUS
ECON1POS
ECON2POS
ECON3POS
ECONOCMD
forcible
ECACTIVE
SACFMCTL
forcible
ECN1UNAV
ECN2UNAV
ECN3UNAV
ENTH
DBC_STAT
DEW_STAT
DDBCSTAT
OAECSTAT
DEC_STAT
EDT_STAT
OAT_STAT
ECONFORC
SFONSTAT
COOL_OFF
OAQLOCKD
ECONHELD
DHDISABL
OAT
forcible
OARH
forcible
OAE
OADEWTMP

Advertisement

Table of Contents
loading

Table of Contents