Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 26

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ENCLOSURE
TYPE
Bhp
ODP
15
TEFC
15
ODP
20
TEFC
20
ODP
25
TEFC
25
ODP
30
TEFC
30
ODP
40
TEFC
40
ODP
50
TEFC
50
ODP
60
TEFC
60
ODP
75
TEFC
75
ODP
100
TEFC
100
LEGEND
Bhp — Brake Horsepower
BkW — Brake Kilowatts
ODP — Open Drip Proof
TEFC — Total Enclosed Fan Cooled
ENCLOSURE
TYPE
Bhp
ODP
7.5
TEFC
7.5
ODP
10
TEFC
10
ODP
15
TEFC
15
ODP
20
TEFC
20
ODP
25
TEFC
25
ODP
30
TEFC
30
ODP
40
TEFC
40
ODP
50
TEFC
50
ODP
60
TEFC
60
LEGEND
Bhp — Brake Horsepower
BkW — Brake Kilowatts
ODP — Open Drip Proof
TEFC — Total Enclosed Fan Cooled
Table 21 — Supply Fan Motor Limitations
NOMINAL
BkW
11.2
11.2
14.9
14.9
18.7
18.7
22.4
22.4
29.8
29.8
37.3
37.3
44.8
44.8
56.0
56.0
74.6
74.6
Table 22 — Power Exhaust and Return Fan Motor Limitations
NOMINAL
BkW
5.60
5.60
7.46
11.48
7.46
11.49
11.2
11.2
14.9
14.9
18.7
18.7
22.4
22.4
29.8
29.8
37.3
37.3
44.8
44.8
MAXIMUM
Bhp
BkW
17.3
12.9
17.2
12.9
22.9
17.1
23.0
17.1
28.7
21.4
28.7
21.4
34.5
25.7
34.5
25.7
43.7
32.6
46.0
34.3
53.9
40.2
57.5
42.9
68.1
50.8
69.0
51.5
84.2
62.8
86.0
64.2
112.2
83.7
114.8
85.6
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with Energy Policy Act (EPACT) Standards
effective October 24, 1997.
MAXIMUM
Bhp
BkW
8.58
6.40
8.62
6.43
8.56
8.57
17.3
12.9
17.2
12.9
22.9
17.1
23.0
17.1
28.7
21.4
28.7
21.4
34.5
25.7
34.5
25.7
43.7
32.6
46.0
34.3
53.9
40.2
57.5
42.9
68.1
50.8
69.0
51.5
NOTES:
1. Extensive motor and electrical testing on the Carrier units has
ensured that the full horsepower range of the motor can be utilized
with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
2. All motors comply with Energy Policy Act (EPACT) Standards
effective October 24, 1997.
26
MAXIMUM AMPS
460 V
575 V
21.7
17.4
20.5
16.6
28.2
22.5
27.3
21.9
35.1
28.2
34.3
27.4
42.1
32.8
41.3
33.0
55.8
44.6
53.5
42.8
69.6
55.2
66.6
53.2
81.7
65.6
81.9
67.5
101.2
80.5
100.7
82.6
132.3
105.8
140.3
110.7
MAXIMUM AMPS
460 V
575 V
11.2
8.6
10.5
8.4
14.5
11.6
14.0
11.3
21.7
17.4
20.5
16.6
28.2
22.5
27.3
21.9
35.1
28.2
34.3
27.4
42.1
32.8
41.3
33.0
55.8
44.6
53.5
42.8
69.6
55.2
66.6
53.2
81.7
65.6
81.9
67.5
RATED
EFFICIENCY
93.0
92.4
93.6
93.0
93.6
93.6
94.1
93.6
94.1
94.1
94.5
94.5
95.0
95.0
95.0
95.4
95.4
95.4
RATED
EFFICIENCY
91.7
91.7
91.7
91.7
93.0
92.4
93.6
93.0
93.6
93.6
94.1
93.6
94.1
94.1
94.5
94.5
95.0
95.0