Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 246

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

Table M — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
Wire Type
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
MS/TP
Network (RS-485)
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
Local Access to the UPC Open Controller
The user can use a BACview
the Virtual BACview software as a local user interface to an
Open controller. These items let the user access the controller
network information. These are accessory items and do not
come with the UPC Open controller.
The BACview
unit connects to the local access port on the
6
UPC Open controller. See Fig. M. The BACview software
APPENDIX F — BACNET COMMUNICATION OPTION (CONT)
Description
handheld keypad display unit or
6
Fig. M — BACview
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
W221P-22227
W241P-2000F
W184C-2099BLB
must be running on a laptop computer that is connected to the
local access port on the UPC Open controller. The laptop will
require an additional USB link cable for connection.
See the BACview Installation and User Guide for instructions
on connecting and using the BACview
To order a BACview
6
Products i-Vu Open Control System Master Prices.
Device Connection
6
246
Contractors
Belden
RMCORP
Wire and Cable
25160PV
CLP0520LC
82841
25120-OR
6302UE
21450
device.
6
Handheld (BV6H), consult Commercial
CLP0442

Advertisement

Table of Contents
loading

Table of Contents