Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 58

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

A1
MM
4
6
5
A2
A3
MM
3
1
2
A4
POWER
BOX
Controlling Output
Contactor
Circuit
Software
Board
Conrolled
A
CONDFAN1
MBB Rly 6
OFC1
A
CONDFAN2
MBB Rly 5
OFC2
B
CONDFAN3
RCB Rly 1
OFC3
B
CONDFAN4
RCB Rly 2
OFC4
Common,
M.M.=YES
or NO
Contactor
Software Pts
# of Fans ON
Stage 1A OFC1
CONDFAN1
1
Stage 1B OFC3
CONDFAN3
1
Stage 2A OFC2
CONDFAN2
2
Stage 2B OFC4
CONDFAN4
2
Stage 3A OFC1,2
CONDFAN1,2
3
Stage 3B OFC3,4
CONDFAN3,4
3
LEGEND
MM
— Motormaster
®
Control
OFC
— Outdoor Fan Contactor
OFM
— Outdoor Fan Motor
Fig. 7 — 75-Ton High Efficiency and 90 to 120-Ton Standard Efficiency Unit Condenser Fan Staging Sequence
B4
Circuit B
Coils
B3
B2
Circuit A
Coils
B1
OFM(s)
Controlled
Logic
OFM2
See Table
OFM 1,3
See Table
OFM5
See Table
OFM 4,6
See Table
Fans ON
Ckt A # Fans ON Ckt B # Fans ON
Ckt A on. Stage up by individual circuit when SCTA > SCT_MAX Stage up to Stage 2A when SCTA>SCT_MAX
OFM2
1
0
Ckt Bon. Stage up by individual circuit when SCTB > SCT_MAX
OFM5
0
1
OFM1,3
2
0
Stage up by individual circuit when SCTA/B > SCT_MAX
OFM4,6
0
2
Stage down by individual circuit when SCTA/B < SCT_MIN
OFM1,2,3
3
0
Stage up & down by individual circuit
OFM4,5,6
0
3
Up if SCTA/B > SCT_MAX, Down if SCTA/B<SCT_MIN
Applicable Units
Tonnage
Efficiency
75
High
90
Standard
105
Standard
120
Standard
Staging Logic
Stage up to Stage 2B when SCTB>SCT_MAX
Stage up to Stage 3A when SCTA>SCT_MAX
Stage up to Stage 3B when SCTB>SCT_MAX
Stage Up Logic
Stage Down Logic
Stage down, OFC1 off, when Ckt A goes off.
Stage down, OFC3 off, when Ckt B goes off.
Stage down to Stage 1A when SCTA< SCT_MIN
Stage down to Stage 1B when SCTB < SCT_MIN
Stage down to Stage 2A when SCTA<SCT_MIN
Stage down to Stage 2B when SCTB<SCT_MIN