Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 263

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
HEAT (CONT)
SG.CF (CONT)
SW.H.T
SW.L.T
HT.P
HT.D
HT.TM
HH.CF
HW.P
HW.I
HT.D
HT.TM
ACT.C
SN.1.1
SN.1.2
SN.1.3
SN.1.4
C.A.L1
SN.2.1
SN.2.2
SN.2.3
SN.2.4
C.A.L2
SN.3.1
SN.3.2
SN.3.3
SN.3.4
C.A.L3
SN.4.1
SN.4.2
SN.4.3
SN.4.4
C.A.L4
SP
SP.CF
SP.SV
SP.S
SP.LO
SP.HI
SP.SP
SP.MN
SP.MX
SP.FS
SP.RS
SP.RT
SP.LM
SP.EC
S.PID
SP.TM
SP.P
SP.I
SP.D
ECON
EC.EN
EC.MN
EC.MX
E.TRM
E.SEL
DDB.O
OA.E.C
OA.EN
OAT.L
O.DEW
ORH.S
CFM.C
OCF.S
O.C.MX
O.C.MN
O.C.DB
OA.RR
OA.MP
EN.DO
E.SAC
S.MX.C
S.M.DB
E.CFG
E.P.GN
E.RNG
E.SPD
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
HEATING CONFIGURATION
STAGED HEAT CONFIGS
Limit Switch High Temp
Limit Switch Low Temp
Heat Control Prop. Gain
Heat Control Derv. Gain
Heat PID Rate Config
HYDRONIC HEAT CONFIGS
Hydronic Ctl.Prop. Gain
Hydronic Ctl.Integ. Gain
Hydronic Ctl.Derv. Gain
Hydronic PID Rate Config
HYDR. HEAT ACTUATOR CONFIGS
Hydronic Ht.Serial Num.1
Hydronic Ht.Serial Num.2
Hydronic Ht.Serial Num.3
Hydronic Ht.Serial Num.4
Hydr.Ht.Ctl.Ang Lo Limit
Humd/HTC2 Ser Num 1
Humd/HTC2 Ser Num 2
Humd/HTC2 Ser Num 3
Humd/HTC2 Ser Num 4
Humd/HTC2 Ctl Ang Lo Lim
HTC3 Serial Number 1
HTC3 Serial Number 2
HTC3 Serial Number 3
HTC3 Serial Number 4
HTC3 Ctrl Angle Lo Limit
HTC4 Serial Number 1
HTC4 Serial Number 2
HTC4 Serial Number 3
HTC4 Serial Number 4
HTC4 Ctrl Angle Lo Limit
SUPPLY STATIC PRESS.CFG.
Static Pressure Control
Staged Air Volume Ctrl
Static Pressure Sensor
Static Press. Low Range
Static Press. High Range
Static Pressure Setpoint
VFD Minimum Speed
VFD Maximum Speed
VFD Fire Speed Override
Stat. Pres. Reset Config
SP Reset Ratio
SP Reset Limit
SP Reset Econo.Position
STAT.PRESS.PID CONFIGS
Stat.Pres.PID Run Rate
Static Press. Prop. Gain
Static Press. Intg. Gain
Static Press. Derv. Gain
ECONOMIZER CONFIGURATION
Economizer Installed?
Economizer Min.Position
Economizer Max.Position
Economzr Trim For SumZ ?
Econ ChangeOver Select
Diff Dry Bulb RAT Offset
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare Value
High OAT Lockout Temp
OA Dewpoint Temp Limit
Outside Air RH Sensor
OUTDOOR AIR CFM CONTROL
Outdoor Air CFM Sensor
Economizer Min.Flow
IAQ Demand Vent Min.Flow
Econ.Min.Flow Deadband
OACFM Econ Ctrl Run Rate
OACFM Econ Ctrl Min Pos
Enable DCFM/OACFM Clamp
Enable Single Act CFM
Single Act. Max CFM
Single Act. Max CFM DB
ECON.OPERATION CONFIGS
Economizer Prop.Gain
Economizer Range Adjust
Economizer Speed Adjust
RANGE
80 to 210 dF
80 to 210 dF
0 to 1.5
0 to 1.5
30 to 300 sec
0 to 1.5
0 to 1.5
15 to 300 sec
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 - 9999
0 - 254
0 - 90
0 - 9999
0 - 6
0 - 9999
0 - 254
0 - 90
0 - 9999
0 - 6
0 - 9999
0 - 254
0 - 90
Disable/Enable
Disable/Enable
Disable/Enable
-10 to 0 in. wg
0 to 10 in. wg
0 to 5 in. wg
0 to 100 %
0 to 100 %
0 to 100 %
0 to 4
0 to 2 in.wg
0 to 2 in.wg
0 to 100 %
5 to 120 sec
0 to 5
0 to 2
0 to 5
No/Yes
0 to 100 %
0 to 100 %
No/Yes
0 to 3 (multi-text strings)
0, -2, -4, -6
1 to 5 (multi-text strings)
18 to 28
-40 to 120 dF
50 to 62 dF
Disable/Enable
0 to 2
0 to 20000 cfm
0 to 20000 cfm
200 to 1000 cfm
3 to 120 sec
0 to 10 %
No/Yes
No/Yes
0 to 20000 cfm
0 to 5000 cfm
0.7 to 3
0.5 to 5 ^F
0.1 to 10
CL-7
DEFAULT
SETTING
170*
160*
1
1
90
1
1
1
90
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Disable
Disable
Disable
0
5
1.5
20
100
100
0
0.2
0.75
5
7
0.5
0.5
0.3
Yes
5
98
Yes
0
0
4
24
60
55
Disable
0
2000
0
400
20
0
Yes
No
7500
2500
1
2.5
0.75