ITEM
SG.CF
STAGED HEAT CONFIGS
HT.ST
Modulating Gas Type
CAP.M
Max Cap Change per Cycle
M.R.DB
St.Ht DB min.dF/PID Rate
S.G.DB
St.Heat Temp. Dead Band
RISE
Heat Rise dF/sec Clamp
LAT.L
LAT Limit Config
LIM.M
Limit Switch Monitoring?
SW.H.T
Limit Switch High Temp
SW.L.T
Limit Switch Low Temp
HT.P
Heat Control Prop. Gain
HT.D
Heat Control Derv. Gain
HT.TM
Heat PID Rate Config
HH.CF
HYDRONIC HEAT CONFIGS
HW.P
Hydronic Ctl.Prop. Gain
HW.I
Hydronic Ctl.Integ. Gain
HT.D
Hydronic Ctl.Derv. Gain
HT.TM
Hydronic PID Rate Config
ACT.C
HYDR.HEAT ACTUATOR CFGS.
SN.1.1
Hydronic Ht.Serial Num.1
SN.1.2
Hydronic Ht.Serial Num.2
SN.1.3
Hydronic Ht.Serial Num.3
SN.1.4
Hydronic Ht.Serial Num.4
C.A.L1
Hydr.Ht.Ctl.Ang Lo Limit
SN.2.1
Humd/HTC2 Ser Num 1
SN.2.2
Humd/HTC2 Ser Num 2
SN.2.3
Humd/HTC2 Ser Num 3
SN.2.4
Humd/HTC2 Ser Num 4
C.A.L2
Humd/HTC2 Ctl Ang Lo Lim
SN.3.1
HTC3 Serial Number 1
SN.3.2
HTC3 Serial Number 2
SN.3.3
HTC3 Serial Number 3
SN.3.4
HTC3 Serial Number 4
C.A.L3
HTC3 Ctrl Angle Lo Limit
SN.4.1
HTC4 Serial Number 1
SN.4.2
HTC4 Serial Number 2
SN.4.3
HTC4 Serial Number 3
SN.4.4
HTC4 Serial Number 4
C.A.L4
HTC4 Ctrl Angle Lo Limit
SP
SUPPLY STATIC PRESS.CFG.
SP.CF
Static Pressure Control
SP.SV
Staged Air Volume Ctrl
SP.S
Static Pressure Sensor
SP.LO
Static Press. Low Range
SP.HI
Static Press. High Range
SP.SP
Static Pressure Setpoint
SP.MN
VFD Minimum Speed
SP.MX
VFD Maximum Speed
SP.FS
VFD Fire Speed Override
SP.RS
Stat. Pres. Reset Config
SP.RT
SP Reset Ratio
SP.LM
SP Reset Limit
SP.EC
SP Reset Econo.Position
S.PID
STAT.PRESS.PID CONFIGS
SP.TM
Stat.Pres.PID Run Rate
SP.P
Static Press. Prop. Gain
SP.I
Static Press. Intg. Gain
SP.D
Static Press. Derv. Gain
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION (cont)
EXPANSION
Disable/Enable
Disable/Enable
Disable/Enable
RANGE
UNITS
CCN POINT
0 to 3
HTSTGTYP
5 to 45
%
HTCAPMAX
0 to 5
HT_MR_DB
0 to 5
^F
HT_SG_DB
0.05 to 0.2
HTSGRISE
0 to 20
^F
HTLATLIM
No/Yes
HTLIMMON
80 to 210
dF
HT_LIMHI
80 to 210
dF
HT_LIMLO
0 to 1.5
HT_PGAIN
0 to 1.5
HT_DGAIN
30 to 300
Seconds
HTSGPIDR
0 to 1.5
HW_PGAIN
0 to 1.5
HW_IGAIN
0 to 1.5
HW_DGAIN
15 to 300
Seconds
HOTWPIDR
0 - 9999
HTC1_SN1
0 - 6
HTC1_SN2
0 - 9999
HTC1_SN3
0 - 254
HTC1_SN4
0 - 90
HTC1CALM
0 - 9999
HTC2_SN1
0 - 6
HTC2_SN2
0 - 9999
HTC2_SN3
0 - 254
HTC2_SN4
0 - 90
HTC2CALM
0 - 9999
HTC3_SN1
0 - 6
HTC3_SN2
0 - 9999
HTC3_SN3
0 - 254
HTC3_SN4
0 - 90
HTC3CALM
0 - 9999
HTC4_SN1
0 - 6
HTC4_SN2
0 - 9999
HTC4_SN3
0 - 254
HTC4_SN4
0 - 90
HTC4CALM
STATICFG
STGAVCFG
-10 to 0
in. wg
0 to 10
in. wg
0 to 5
in. wg
10 to 100
%
STATPMIN
0 to 100
%
STATPMAX
0 to 100
%
STATPFSO
0 to 4
SPRSTCFG
in. wg
SPRRATIO
0 to 2
0 to 2
in. wg
SPRLIMIT
0 to 100
%
ECONOSPR
5 to 120
Seconds
SPIDRATE
0 to 5
STATP_PG
0 to 2
STATP_IG
0 to 5
STATP_DG
199
DEFAULT
60,64
0*
60,64
45*
60,64
0.5
60,64
2
60,64-65
0.06
60,64
10
60,64
Yes
60,64,67
170*
60,64,67
160*
60,64,67
1
60,64-65
1
60,64-65
90
60,64
1
60
1
60
1
60
90
60
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
0
60,64
Disable
69,70
Disable
69,70
SPSENS
Disable
69,70
SP_LOW
0
69,70
SP_HIGH
5
69,70
SPSP
1.5
69,70
20
69,70
100
69,70
100
69,70
0
69,70
0.2
69,70
0.75
69,70
5
69
7
69,70
0.5
69,70
0.5
69,70
0.3
69,70
PAGE NO.