Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 201

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
ECON (cont)
ECONOMIZER CONFIGURATION (cont)
EC.DY
T24 Econ Auto-Test Day
EC.TM
T24 Econ Auto-Test Time
BP
BUILDING PRESS. CONFIGS
BP.CF
Building Press. Config
BP.S
Building Pressure Sensor
BP.R
Bldg. Press. (+/-) Range
BP.SP
Building Pressure Setp.
BP.SO
BP Setpoint Offset
B.V.A
VFD/ACTUATOR CONFIG
BP.FS
VFD Fire Speed
BP.MN
VFD Minimum Speed
BP.MX
VFD Maximum Speed
FAN.T
FAN TRACKING CONFIG
FT.CF
Fan Track Learn Enable
FT.TM
Fan Track Learn Rate
FT.ST
Fan Track Initial DCFM
FT.MX
Fan Track Max Clamp
FT.AD
Fan Track Max Correction
FT.OF
Fan Track Internl EEPROM
FT.RM
Fan Track Internal RAM
FT.RS
Fan Track Reset Internal
FAN.C
SUPPLY, RET/EXH FAN CFG
SCF.C
Supply Air CFM Config
REF.C
Ret/Exh Air CFM Config
SCF.S
Supply Air CFM Sensor
RCF.S
Return Air CFM Sensor
ECF.S
Exhaust Air CFM Sensor
B.PID
BLDG.PRESS.PID CONFIGS
BP.TM
Bldg.Pres.PID Run Rate
BP.P
Bldg.Press. Prop. Gain
BP.I
Bldg.Press. Integ. Gain
BP.D
Bldg.Press. Deriv. Gain
D.LV.T
COOL/HEAT SETPT. OFFSETS
L.H.ON
Dmd Level Lo Heat ON
H.H.ON
Dmd Level(+) Hi Heat ON
L.H.OF
Dmd Level(-) Lo Heat OFF
L.C.ON
Dmd Level Lo Cool ON
H.C.ON
Dmd Level(+) Hi Cool ON
L.C.OF
Dmd Level(-) Lo Cool OFF
C.T.LV
Cool Trend Demand Level
H.T.LV
Heat Trend Demand Level
C.T.TM
Cool Trend Time
H.T.TM
Heat Trend Time
DMD.L
DEMAND LIMIT CONFIG.
DM.L.S
Demand Limit Select
D.L.20
Demand Limit at 20 ma
SH.NM
Loadshed Group Number
SH.DL
Loadshed Demand Delta
SH.TM
Maximum Loadshed Time
D.L.S1
Demand Limit Sw.1 Setpt.
D.L.S2
Demand Limit Sw.2 Setpt.
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
IAQ.M
IAQ Demand Vent Min.Pos.
O.C.MX
Economizer Min.Flow
O.C.MN
IAQ Demand Vent Min.Flow
O.C.DB
Econ.Min.Flow Deadband
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
IQ.A.F
IAQ 4-20 ma Fan Config
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION (cont)
EXPANSION
3=Wednesday,
Disable/Enable
-20000 to 20000
-20000 to 20000
-20000 to 20000
Disable/Enable
Disable/Enable
Disable/Enable
RANGE
UNITS
CCN POINT
0=Never,
1=Monday,
2=Tuesday,
4=Thursday,
5=Friday,
6=Saturday,
7=Sunday
0 - 23
0 to 2
BLDG_CFG
0.1 to 0.25
"H2O
BP_RANGE
-0.25 to 0.25
"H2O
0 to 0.5
"H2O
0 to 100
%
BLDGPFSO
0 to 100
%
0 to 100
%
BLDGPMAX
No/Yes
DCFM_CFG
5 to 60
min
DCFMRATE
CFM
DCFMSTRT
0 to 20000
CFM
DCFM_MAX
0 to 20000
CFM
CFM
DCFM_OFF
CFM
DCFM_RAM
No/Yes
DCFMRSET
1 to 2
SCFM_CFG
1 to 2
RECFMCFG
SCFMSENS
RCFMSENS
ECFMSENS
1 to 60
Seconds
0 to 5
BLDGP_PG
0 to 2
0 to 5
BLDGP_DG
0 to 2
^F
0.5 to 20
^F
0.5 to 2
^F
DMDLHOFF
0 to 2
^F
0.5 to 20
^F
0.5 to 2
^F
DMDLCOFF
0.1 to 5
^F
CTRENDLV
0.1 to 5
^F
HTRENDLV
30 to 600
Seconds
CTRENDTM
30 to 600
Seconds
HTRENDTM
0 to 3
DMD_CTRL
0 to 100
%
0 to 99
SHED_NUM
0 to 60
%
0 to 120
Minutes
0 to 100
%
0 to 100
%
0 to 100
%
ECONOMIN
0 to 100
%
OACFMMAX
0 to 20000
CFM
0 to 20000
CFM
OACFMMIN
200 to 1000
CFM
OACFM_DB
0 to 4
0 to 2
201
DEFAULT
T24_ECDY
6=Saturday
T24_ECTM
2
0*
BPSENS
Disable*
0.25
BPSP
0.05
BPSO
0.05
100
BLDGPMIN
10
100
No
15
2000
4000
DCFM_ADJ
1000
0
0
No
2
2
Disable*
Disable*
Disable*
BPIDRATE
10
0.5
BLDGP_IG
0.5
0.3
DMDLHON
1.5
DMDHHON
0.5
1
DMDLCON
1.5
DMDHCON
0.5
1
0.1
0.1
120
120
0
DMT20MA
100
0
SHED_DEL
0
SHED_TIM
6
DLSWSP1
80
DLSWSP2
50
5
IAQMINP
0
2000
0
400
IAQANCFG
0
IAQANFAN
0
PAGE NO.
76
76
82
82
82
28,82
28,82
28,82
28,82
28,82
28,82
28,82
28,83
28,83
28,83
28,82
28,82
28,82
82
82
82
82
82
82
82
82,83
82,83
51,62
51,62
51,62
51,62
51,62
51,62
51,62
51,62
51,62
51,62
54,56
56
56
56
56
56
56
38,86,88
38,86,88,130
38,86,88
38,86,88
86,88
38,86
38,86