Carrier ERVCCSVB1100 Installation Instructions Manual
Carrier ERVCCSVB1100 Installation Instructions Manual

Carrier ERVCCSVB1100 Installation Instructions Manual

Energy / heat recovery ventilator

Advertisement

ERVCCSVB1100, ERVCCSHB1100
HRVCCSVB1100, HRVCCSHB1100
Energy / Heat Recovery Ventilator
NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Fresh air to building port
2. Exhaust air from building port
3. Fresh air from outside port
4. Exhaust air to outside port
Fig. 1 - - ERV/HRV Unit (Top Port)
Installation Instructions
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
PAGE
1
2
2
2
3
Fig. 2 - - ERV/HRV Unit (Side Port)
4

SAFETY CONSIDERATIONS

6
Improper installation, adjustment, alteration, service, maintenance,
6
or use can cause explosion, fire, electrical shock, or other
6
conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency, or your
7
distributor or branch for information or assistance. The qualified
8
installer or agency must use factory- -authorized kits or accessories
8
when modifying this product. Refer to the individual instructions
packaged with kits or accessories when installing.
8
Follow all safety codes. Wear safety glasses, protective clothing
9
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes and the current editions of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety- -alert symbol
When you see this symbol on the unit and in instruction manuals,
be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety- -alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
A08103
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
A05330
.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ERVCCSVB1100 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier ERVCCSVB1100

  • Page 1: Table Of Contents

    ERVCCSVB1100, ERVCCSHB1100 HRVCCSVB1100, HRVCCSHB1100 Energy / Heat Recovery Ventilator Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS ......INTRODUCTION .
  • Page 2: Introduction

    INTRODUCTION ERV/HRV is installed in conjunction with a forced- -air system, unit should be located next to (or close to) the indoor equipment. The Energy/Heat Recovery Ventilator (ERV/HRV) is used to COMPONENT DESCRIPTION exchange indoor stale air with outside fresh air. The unit is equipped with a special energy/heat recovery core which transfers The following listed items are components of ERVCCSHA (See both sensible and/or latent heat between the fresh incoming air and...
  • Page 3: Unit Installation

    UNIT INSTALLATION alone unit. To ensure comfort, this type of application involves running both fresh- -air and return- -air registers (or stale- -air pickup CAUTION registers) throughout the home. Fresh- -air registers are normally located in bedrooms, dining room, living room, and basement. It is recommended that registers be UNIT DAMAGE HAZARD placed 6 to 12- -in.
  • Page 4: Wall Control

    Connect Ducts to ERV/HRV To connect condensate drain, proceed as follows: 1. Punch out holes in foam insulation and door, then insert CAUTION sleeved grommets into bottom of unit using the gasket washer and nut. (See Fig. 9.) 2. Cut two sections of plastic tubing, about 12- -in. / 305mm PROPERTY DAMAGE HAZARD long and attach them to each drain.
  • Page 5 OneTouch Control between wall control and ERV/HRV connector following color code. (See Fig. 5 and 10.) Replace top cover assembly. The OneTouch Control can be used as the primary wall control for NOTE: ERV/HRV wall control and circuit board operate on the ERV/HRV.
  • Page 6: Operating The Erv/Hrv With The Infinity Control

    OPERATING THE ERV/HRV WITH ACCESSORIES THE INFINITY CONTROL 20 Minute Timer The ventilator has four settings in heating mode and three settings A push button timer can be used to override the wall control and in cooling mode. put the ERV/HRV into high speed for 20 minutes. Connect switches in parallel and connect leads to ERV/HRV terminals I, Heating: OC, and OL (See Fig.
  • Page 7: Balancing Erv/Hrv

    BALANCING ERV/HRV Before proceeding with balancing, all windows, doors, and fireplace flues should be tightly closed. No exhaust systems such as Balancing intake and exhaust airflow is very important for proper range top exhausts, dryer exhaust, fume hoods, bath or roof fans system operation and optimum performance when applying an should be in operation.
  • Page 8: Ventilation Evaluation

    VENTILATION EVALUATION between Red and Gray wires on Molex plug (pins 1 and 4) and blower motor runs in low- -speed operation. CAUTION CARE AND MAINTENANCE Door UNIT DAMAGE HAZARD ERV/HRV door can be removed by unlatching brief case style Failure to follow this caution may result in reduced unit latches, then slide door to the right and remove it from hinges.
  • Page 9: Troubleshooting

    TROUBLESHOOTING NOTE: The core should only be serviced when outdoor temperature is 60°F to 75°F (16°C to 24°C) and it is dry. NOTE: Reference Table 5 Troubleshooting Chart CAUTION This can be a quick guide in resolving unit problems. It is also recommended to review and understand Wall Control Board Operation and Care and Maintenance sections before continuing.
  • Page 10 If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the unit the problem occurs. Table 5 – Troubleshooting LED flashes GREEN. Thermistor error. Reference Table 6 for proper temperature vs.
  • Page 11 Table 6 – Temperature / Ohm Relationship Table 7 – Defrost Cycle TEMP . (°F / °C) RESISTANCE (OHMS) HRV DEFROST CYCLES Operation time (min.) --- 9 / --- 23 78330 Outside Temp Defrosting between each --- 8 / --- 22 74610 °F / °C (minutes)
  • Page 12 CONNECTION DIAGRAM : USE SPECIFIED UL LISTED/CSA COLOR CODE CERTIFIED LINE FUSE. Type 3AG, Littelfuse no 312003. BLACK Line voltage factory wiring BLUE 2. If any of the original wire, as supplied, must be BROWN replaced, use the same equivalent wire. Class 2 low voltage factory wiring GREEN 3.
  • Page 13 LOGIC DIAGRAM 120V, 60Hz 120V, 60Hz Neutral Line HI MED J10-2 J10-1 120V J9-1 Exhaust fan motor J9-2 J5-1 106V J5-2 J5-3 J9-3 Exhaust fan motor J9-4 capacitor J7-2 J7-1 Supply fan motor J4-1 J4-2 J4-3 Supply fan motor capacitor J6-2 J6-1 J12-5...
  • Page 14 Canada. HRVCCSHB1100 Catalog No: ERVHRV ---3SI Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 05/10 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

This manual is also suitable for:

Ervccshb1100Hrvccsvb1100Hrvccshb1100

Table of Contents