Channel change completed flag
When changing a channel to perform the offset/gain setting, use Channel change completed flag (XB) as an interlock
condition to turn on and off 'Channel change request' (YB). When the offset/gain setting is configured from the offset/gain
setting window of an engineering tool, the setting is performed properly on the window. Therefore, a program is not required to
perform the setting.
When the offset/gain setting is configured by reusing a program that is used in a temperature input module of MELSEC-Q
series, check that this signal is used as the interlock.
For the programs of a temperature input module of MELSEC-Q series, refer to the following.
 MELSEC-Q Channel Isolated Thermocouple Input Module User's Manual
 MELSEC-Q Channel Isolated RTD Input Module User's Manual
'CH1 Offset/gain setting mode
(offset specification) (Un\G4132),
'CH1 Offset/gain setting mode
(gain specification) (Un\G4133)
'Channel change completed flag' (XB)
'Channel change request' (YB)
■Device number
The following shows the device number of this input signal.
Signal name
Channel change completed flag
Controlled by the temperature input module
Controlled by the program
Offset setting/gain setting channel
ON
OFF
ON
OFF
CH1
CH2
CH3
XB
OFF
OFF
CH4
CH5
CH6
CH7
CH8
APPX
93
Appendix 2 I/O Signals