Mitsubishi Electric MELSEC iQ-R Series User Manual page 129

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Scaling value
The value after scale conversion by means of the scaling function is stored in 16-bit signed binary.
b15 b14 b13 b12 b11 b10 b9
(2)
(1) Data section
(2) Sign bit 0: Positive, 1: Negative
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling value
CH Scaling value (in Q compatible mode)
With no scaling function used, the same value as 'CH1 Measured temperature value' (Un\G400) is stored.
CH1 Logging hold flag
The logging holding status can be checked.
For details on the logging function, refer to the following.
Page 40 Logging Function
Monitor value
0
1
As data collection in 'CH1 Logging data' (Un\G10000 to Un\G10999) comes to a halt, this flag turns to ON (1).
When logging restarts by changing 'CH1 Logging hold request' (Un\G471) from ON (1) to OFF (0), 'CH1 Logging hold flag'
(Un\G409) is turned to OFF (0).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging hold flag
CH Logging hold flag (in Q compatible mode)
b8
b7
b6
b5
b4
b3
b2
(1)
CH1
CH2
402
602
50
51
CH1
CH2
409
609
1016
1017
b1
b0
CH3
CH4
CH5
802
1002
1202
52
53
54
Description
OFF
ON
CH3
CH4
CH5
809
1009
1209
1018
1019
1020
CH6
CH7
CH8
1402
1602
1802
55
56
57
CH6
CH7
CH8
1409
1609
1809
1021
1022
1023
APPX
Appendix 3 Buffer Memory Areas
A
127