Mitsubishi Electric MELSEC iQ-R Series User Manual page 57

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting procedure
To use the logging read function, both the logging read function and the interrupt setting must be set.
1.
Set "Condition target setting" to "Logging read".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Interrupt setting]
2.
Set "Conversion enable/disable setting" to "Conversion enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Conversion
enable/disable setting function]
3.
Set "Logging enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting]  [Logging
function]
4.
Set the target data to be logged in "Logging data setting".
5.
Set the cycle to store the logging data to "Logging cycle setting value".
6.
Set "Logging loading enable/disable setting" to "Enable".
7.
Set the number of logging points that generate a read interrupt in "Logging read points setting value".
Setting example
When an interrupt program, which is executed when the data of CH1 Logging read points monitor value is logged, is assigned
to the interrupt pointer I50 for the thermocouple input module
• Label settings
Classification
Label name
Module Label
RCPU.stSM.bAlways_ON
RCPU.stSM.bAfter_RUN1_Scan_ON
R60TDG_1.unInterruptFactorMask_D[1].0
R60TDG_1.unInterruptFactotDetectionFlag
R60TDG_1.unInterruptFactorResetRequest_D[1].0
R60TDG_1.stnMonitor_D[1].wThisLoggingLoadPointer_D
R60TDG_1.stnMonitor_D[1].uLoggingLLoadPointsMonitorValue
Labels to be defined
Define global labels as shown below:
Description
Always ON
ON for one scan after RUN
Interrupt factor mask
Interrupt factor detection flag
Interrupt factor reset request
CH1 Current logging read pointer
CH1 Logging read points monitor value
1.10 Logging Function
1
Device
SM400
SM402
U0\G124
U0\G4
U0\G156
U0\G438
U0\G440
1 FUNCTIONS
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60td8-gR60rd8-g

Table of Contents