Mitsubishi Electric MELSEC iQ-R Series User Manual page 157

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Logging read points setting value
An interrupt is generated to the CPU module each time the number of data logging reaches a predetermined number of
points.
For details on the logging function, refer to the following.
Page 40 Logging Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging read points setting value
CH Logging read points setting value (in Q
compatible mode)
■Setting range
The possible range is from 1 to 1000.
Setting a value out of the range causes a logging read points setting value range error (error code: 1D9H). Logging cannot
be performed.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 100 for all the channels.
CH1 Scaling enable/disable setting
Set whether to enable or disable the scaling.
For details on the scaling function, refer to the following.
Page 23 Scaling Function
Setting value
0
1
Setting a value other than the above causes a scaling enable/disable setting range error (error code: 1A0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling enable/disable setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all the channels.
CH1
CH2
CH3
545
745
945
1208
1209
1210
Setting content
Enable
Disable
CH1
CH2
CH3
546
746
946
CH4
CH5
CH6
1145
1345
1545
1211
1212
1213
CH4
CH5
CH6
1146
1346
1546
Appendix 3 Buffer Memory Areas
CH7
CH8
1745
1945
1214
1215
A
CH7
CH8
1746
1946
APPX
155