Mitsubishi Electric MELSEC iQ-R Series User Manual page 123

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Level data 0 to 9
This area stores data to be monitored when a level trigger of the logging function is used. Ten types of data are available:
'Level data 0' (Un\G90) to 'Level data 9' (Un\G99). These are useful, for example, to generate triggers while monitoring the
values of devices other than the temperature input module.
For details on the logging function, refer to the following.
Page 40 Logging Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
0
Level data
90
Level data (in Q
1072
compatible mode)
■Setting range
The possible range is from -32768 to 32767.
■Default value
The default value is 0 for all the channels.
Interrupt factor mask [n]
Set Interrupt factor mask to be used.
Setting value
0
1
When 'Interrupt factor mask [n]' (Un\G124 to Un\G139) is changed to Mask clear (Interrupt used) (1) and an interrupt factor
occurs, an interrupt request is sent to the CPU module. When the set value is two or larger, the setting is regarded as Mask
clear (Interrupt used) (1).
"n" indicates an interrupt setting number. (n = 1 to 16)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
1
Interrupt factor mask [n]
124
Interrupt factor mask [n] (in Q
4032
compatible mode)
■Default value
The default value is Mask (Interrupt unused) (0) for all the channels.
1
2
3
91
92
93
1073
1074
1075
2
3
4
5
6
125
126
127
128
129
4033
4034
4035
4036
4037
4
5
6
94
95
96
1076
1077
1078
Setting content
Mask (Interrupt unused)
Mask clear (Interrupt used)
7
8
9
10
11
130
131
132
133
134
4038
4039
4040
4041
4042
Appendix 3 Buffer Memory Areas
7
8
9
97
98
99
1079
1080
1081
12
13
14
15
16
135
136
137
138
139
4043
4044
4045
4046
4047
APPX