CH1 Scaling width lower limit value
Set a lower limit on the width of scale conversion.
For details on the scaling function, refer to the following.
Page 23 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling width lower limit value
CH Scaling width lower limit value (in Q
compatible mode)
■Setting range
The possible range is from -32768 to 32767.
A channel where the set values do not satisfy the condition "Scaling upper limit value  Scaling lower limit value" causes a
scaling setting range error (error code: 1A3H).
When 'CH1 Scaling enable/disable setting' (Un\G546) is set to Disable (1), the setting for 'CH1 Scaling lower limit value'
(Un\G550) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all the channels.
APPX