Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Gain temperature setting value
As Channel change request (YB) is turned on and off in offset/gain setting mode, the measured temperature value is
corrected by a value written in this area.
Specify the value of a 16-bit signed binary number.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Gain temperature setting value
CH Gain temperature setting value (in Q
compatible mode)
■Setting range
• Thermocouple input module
Input range
K thermocouple
E thermocouple
J thermocouple
T thermocouple
B thermocouple
R thermocouple
S thermocouple
N thermocouple
• RTD input module
Input range
Pt100 (-200 to 850)
Pt100 (-20 to 120)
Pt100 (0 to 200)
JPt100 (-180 to 600)
JPt100 (-20 to 120)
JPt100 (0 to 200)
Ni100 (-60 to 250)
Pt50 (-200 to 650)
Setting a value out of the range causes an offset/gain temperature setting value range error (error code: 1ECH).
'CH1 Offset temperature setting value' (Un\G562) and 'CH1 Gain temperature setting value' (Un\G564) must be set to be
within the following temperature input range:
• Gain temperature set value - Offset temperature set value > 0.1
A channel where the set value is out of the above range causes an offset/gain temperature setting error (error code: 1E9H).
■Default value
The default value is 0 for all the channels.
• An effective way to achieve high accuracy is to set up error correction in 'CH1 Offset temperature setting
value' (Un\G562) and 'CH1 Gain temperature setting value' (Un\G564) assuming the minimum and
maximum temperatures of the used range.
• Configure 'CH1 Offset temperature setting value' (Un\G562) and 'CH1 Gain temperature setting value'
(Un\G564) while reading out measured temperature values.
APPX
160
Appendix 3 Buffer Memory Areas
CH1
CH2
CH3
564
764
964
29
31
33
Setting range
-2700 to 13700
-2700 to 10000
-2100 to 12000
-2700 to 4000
0 to 18200
-500 to 17600
-500 to 17600
-2700 to 13000
Setting range
-2000 to 8500
-200 to 1200
0 to 2000
-1800 to 6000
-200 to 1200
0 to 2000
-600 to 2500
-2000 to 6500
CH4
CH5
CH6
1164
1364
1564
35
37
39
CH7
CH8
1764
1964
41
43