Details of input signals

The following describes the details of the input signals for a temperature input module which are assigned to the CPU module.
The I/O numbers (X/Y) described in this section are for the case when the start I/O number of a temperature input module is
set to 0.
This section describes buffer memory addresses for CH1. For details on the buffer memory addresses after
CH2, refer to the following.
Page 99 Buffer Memory Areas
Module READY
Module READY (X0) turns on to indicate the preparation for the temperature conversion is completed after the power-on or
after the reset operation of the CPU module, and the temperature conversion is performed.
In the following cases, 'Module READY' (X0) turns off.
• In the offset/gain setting mode (In this case, the temperature conversion is performed.)
• When a watchdog timer error has occurred in the temperature input module (In this case, the temperature conversion is not
performed.)
■Device number
The following shows the device number of this input signal.
Signal name
Module READY
Operating condition setting completed flag
When changing values of the buffer memory, use Operating condition setting completed flag (X9) as an interlock condition to
turn on and off 'Operating condition setting request' (Y9). For the buffer memory areas which require turning on and off of
'Operating condition setting request' (Y9) to enable the changed values, refer to the following.
Page 99 Buffer Memory Areas
When 'Operating condition setting completed flag' (X9) is off, the temperature conversion is not performed.
When 'Operating condition setting request' (Y9) is on, 'Operating condition setting completed flag' (X9) turns off.
ON
'Module READY' (X0)
'Operating condition setting
completed flag' (X9)
'Operating condition setting
request' (Y9)
'Conversion completed flag'
(XE)
■Device number
The following shows the device number of this input signal.
Signal name
Operating condition setting
completed flag
CH1
CH2
CH3
X0
Controlled by the temperature input module
Controlled by the program
ON
OFF
ON
ON
OFF
CH1
CH2
CH3
X9
CH4
CH5
CH6
ON
OFF
ON
CH4
CH5
CH6
CH7
CH8
CH7
CH8
APPX
91
Appendix 2 I/O Signals