■Setting the monitoring condition
• Set a condition to generate a hold trigger in 'CH1 Level trigger condition setting' (Un\G540).
Setting value
Level trigger (condition:
Rise) (1)
Level trigger (condition:
Fall) (2)
Level trigger (condition:
Rise and fall) (3)
• Set a value where a hold trigger is generated to 'CH1 Trigger setting value' (Un\G542).
Item
'CH1 Trigger setting value' (Un\G542)
The following figure shows the relation between setting items to be configured for the initial setting of a level
trigger.
To generate a hold trigger when a value in CH1 Measured temperature value is greater than 1000, set as
follows.
• 'CH1 Level trigger condition setting' (Un\G540): Rise (1)
• 'CH1 Trigger data' (Un\G541): 400
• 'CH1 Trigger setting value' (Un\G542): 1000
1 FUNCTIONS
50
1.10 Logging Function
Description
Stored value of a buffer memory area to be monitored
(a)
Trigger setting
value
(a) A hold trigger is generated when the relation between the values changes
from "Stored value of a buffer memory area to be monitored  Trigger
setting value" to "Stored value of a buffer memory area to be monitored >
Trigger setting value".
(b) A hold trigger is generated when the relation between the values changes
from "Stored value of a buffer memory area to be monitored  Trigger
setting value" to "Stored value of a buffer memory area to be monitored <
Trigger setting value".
CH
setting
CH
Trigger data
(Rise and fall (3))
Set the address of a buffer memory area to be monitored.
CH
Measured
temperature value
CH
Scaling value
Level data
(b)
Time
Setting range
-32768 to 32767
Level trigger condition
Set the condition.
>
(Rise (1))
<
CH
Trigger setting value
(Fall (2))
> or <
-32768 to 32767
A hold trigger is generated under the condition (a).
A hold trigger is generated under the condition (b).
A hold trigger is generated under the condition (a)
or (b).
The condition is
established.
Set a reference value to generate a trigger.
A trigger is
generated.