Disconnection detection automatic clear enable/disable setting
Set whether to enable or disable an automatic clear of disconnection detection of the disconnection detection function.
Setting value
0
1
Setting a value other than in the table above results in operation with Disable (1).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Disconnection detection automatic clear enable/
disable setting
Disconnection detection automatic clear enable/
disable setting (in Q compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all the channels.
CH1 Measured temperature value
The converted measured temperature value is stored in 16-bit signed binary.
b15 b14 b13 b12 b11 b10 b9
(2)
(1) Data section
(2) Sign bit 0: Positive, 1: Negative
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Measured temperature value
CH Measured temperature value (in Q
compatible mode)
■Refreshing cycle
If averaging processing is performed, values are updated at every averaging process cycle, but if not performed, values are
updated at every sampling cycle.
APPX
126
Appendix 3 Buffer Memory Areas
CH1
CH2
303
157
b8
b7
b6
b5
b4
b3
b2
(1)
CH1
CH2
400
600
11
12
Description
Enable
Disable
CH3
CH4
CH5
b1
b0
CH3
CH4
CH5
800
1000
1200
13
14
15
CH6
CH7
CH8
CH6
CH7
CH8
1400
1600
1800
16
17
18

Hide quick links: