Setting example
■Example 1
This example assumes that the thermocouple input module is used with the following settings for the channel where a K
thermocouple (-270 to 1370) is connected.
• "Scaling enable/disable setting": "Enable"
• "Scaling range upper limit value": 5000
• "Scaling range lower limit value": -1000
• "Scaling width upper limit value": 100
• "Scaling width lower limit value": 0
A measured temperature value and scaling value become as follows.
Scaling value
Scaling width upper limit
value 100
Scaling width lower limit
value 0
-100
-270
Scaling range lower limit
value -1000
-270
K thermocouple
Scaling range lower limit value
0
Scaling width lower limit value
Temperature input value
-100.1 or lower
-100.0
50.0
200.0
350.0
500.0
500.1 or higher
100
0
0
500
Scaling range upper limit
value 5000
-100
500
Scaling range
Scaling width upper limit value
Measured temperature value
-1001 or lower
-1000
500
2000
3500
5000
5001 or higher
1370
Input temperature ()
1370
Scaling range upper limit value
100
Scaling value
0
0
25
50
75
100
100
1 FUNCTIONS
25
1.5 Scaling Function
1