Grundfix Plus-Control – Modell 4987.41
Terminal strip order
Pos.
Cable
1
black – factory-fitted
2
red – factory-fitted
3
black – factory-fitted
4
red – factory-fitted
5
green
6
yellow
7
8
9
10
11
brown
12
white
Terminal strip order 20 m cable
Pos.
Cable
5
Conductor 3
6
Conductor 4
11
Conductor 2
12
Conductor 1
Alarm and fault indicating contacts
The control unit is provided as standard with two potential-free outlets, through which other optional acoustic and optical alarm
devices can be connected. Both contacts work as a closing contact. In case of backflow, the alarm contact (clamping strip connec-
tion (7/8) is closed in "Back" mode. The error signal contact (clamping strip connection (9/10) closes in "Error" mode when an oper-
ating fault is reported. When allocating the contacts, you must ensure that a maximum current of 500 mA is not exceeded. In addi-
tion, only purely ohmic loads should be connected. An allocation of the potential-free outlets must only take place using a safety
low voltage and galvanic separation of the network. The use of a safety transformer in accordance with VDE 0551 or DIN/EN 60742
is permitted.

Technical data

Switching power supply
LCD
RTC real time clock
Battery
Log
Potential-free relay outlet
Casing
Protection class in acc.
With VDE 0100
Battery fuse
Motor fuse
Closing time in case of
backflow
15 volt mains connection
15 volt mains connection
Battery connection
Battery connection
Motor connection
Motor connection
Signalises backflow
Signalises backflow
Signalises fault
Signalises fault
Pressure switch
Pressure switch
Motor connection
Motor connection
Pressure switch
Pressure switch
88-264VAC 50 / 60Hz
20 x 2 with lighting
carry-over 30 days
12V /1.2 Ah; integrated charge and test electronics for battery operation for up to 24 hours in the
case of power failure
512 events
Backflow and fault
Plastic casing 201 x 151 x 80 mm without hinge and PG screw fitting
Control unit casing IP54; Grundfix Control IP
4 A - inactive
4 A - inactive
In both mains and battery operation approx. 10 seconds
Functions
Functions
71
Indication on the connection strip
GND
+ 15V
GND
+ AKKU (battery)
Motor -
Motor +
RÜCK (backflow)
RÜCK (backflow)
STÖR (fault)
STÖR (fault)
Sensor
Sensor
Indication on the connection strip
Motor -
Motor +
Sensor
Sensor
www.viega.com