Viega Grundfix Plus-Control Manual page 75

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 66
Grundfix Plus-Control – Modell 4987.41
Overview of the menu order - Selection with T1
Press T1
Diplay
Normalbetrieb
RV-geöffnet
(Norm. operation
NRV open)
Wartung
1x
(Maintenance)
Selbsttest
Ein / Aus
2x
(Self test on/off)
Uhr Selbsttest
einstellen
3x
(Time Self test
adjust)
Datum / Uhr
einstellen
4x
(Date/time
adjust)
Ereignisspeicher
5x
(Event memory)
Softwareversion
6x
(Software vers.)
Betriebsstunden
7x
(Operating hours)
Sprache einstellen
8x
(Language adjust)
Normalbetrieb
RV-geöffnet
9x
(Norm. operation
NRV open)
Normalbetrieb
RV-geöffnet
(Norm. operation
NRV open)
Normalbetrieb
RV-geöffnet
(Norm. operation
NRV open)
Special functions in normal operation
QAcoustic signals in case of backflow or fault are switched off by pressing T1 once and confirmed with T3.
Q
During normal operation, the motor-driven flap can be opened and closed by pressing T2.
Q
Q
If no entry is made for more than 1 minute after pressing T1, the display switches to »Normalbetrieb« (Norm. operation).
Q
Q
Reading of the log
The "log" menu enables the display of 512 control unit-relevant events with date and time.
When the memory is full, the oldest event is overwritten.
The following events are displayed
Neu-Init (Reinit)
Q
Q
Motorstörung (Motor fault)
Q
Q
Wartung durchgeführt (Perform maintenance)
Q
Q
Datum-Umstellung (Date adjustment)
Q
Q
QZwangsgeöffnet (Positive opening)
Q
RV-schliesst (NRV closes)
Q
Q
QAbschaltung Akku (Battery shut-off)
Q
T3
T1
Open/Close motor-driven
flap
0n/Off
0n/Off
up
down
up
down
back to log
Select languages
Select languages backwards
forward
Press once
– Test BFV closes
Press once
– Test BFV opens
T2
Return to normal opera-
tion after maintenance
Save and return to normal
operation
Call up one after another:
Hours/Minutes
Call up one after another:
Date / Time
Call up the events one
after another
Back to software version
Back to operating hours
Save and return to "select
language"
Press once
– Commissioning
BFV closes/BFV opens
Reset or initialisation of the control unit
Motor fault
Successful maintenance
Changing of the date
Forced opening of the motor-driven flap in case of backflow
Motor-driven flap has been closed because the battery power is less
than 11.8 V in battery operation
Shut-down because the battery power is less than 10.5 V in battery
operation
75
T3
Result
Maintenance successfully completed
Autotest active/inactive
Clock set
Current date/time
(for log display and autotest)
Tip: The adjustment from Daylight
Saving Time and back is carried out
manually.
Log display
Display of current software
Display operating hours
Display in selected language
Menu display starts at the beginning
Test BFV closed
Normal operation BFV open
Normal operation BFV open