Overview of error messages on the display

No.
Display
Akkubetrieb
RV-geöffnet
1
(Battery operation
NRV open)
Fehler Akku / Akku
einlegen
2
(Battery error / Insert
battery)
Fehler Akku / Akku
tauschen
3
(Battery error / replace
battery)
Fehler Motorstörung
RV-geöffnet
(Error motor fault
NRV open)
4
Rückstau
Notverschl schließen
(Back pressure
close emergency lock)
Inbetriebnahme
Fehler 1 /
Motorstörung
5
(Commissioning
Error 1 / motor fault)
Rückstau
RV-Geschlossen
(Anzeige, obwohl kein
Rückstau ansteht)
6
Backflow
(Back pressure
NRV closed)
(Display although
there is no backflow
occurring)
The components integrated into the cover cannot be replaced individually
1)
Error 4 is displayed if a backflow is recognised in normal operation and the battery motor-driven flap cannot be closed due to an
motor defect or foreign body blocking it.
Error 5 is displayed if a defect is recognised during a self-test.
If the control unit does not switch automatically to »Normalbetrieb« (normal operation) after an attempted troubleshooting proce-
dure, a specialist should be consulted to restore the protection against backflow.
Troubleshooting by non-specialised persons
In case of a fault, the operator of the system, who is not normally a specialist, should proceed as follows
QTurn off the alarm tone
Q
Displayed Fault no. 1
Q
Q
Displayed Fault no. 4 / 5
Q
Q
QAll other errors in case
Q
Possible cause
Power outage, automatic
cut-out has been activated
Battery is missing or
battery fuse or cabling is
defective
Motor fuse and / or battery
fuse defective
– Motor defective
– Motor spindle broken
– Motor-driven flap blocked
– Motor valve blocked
– Motor / mechanism
defective
Pressure switch defective.
Select »Ton Aus« "Sound Off" with T1 menu and confirm with T3.
Check 230 V power supply (plug) and circuit breakers.
Trigger a reset with T3: If the engine is intact, the motor-driven flap will open and close three
times. If the blockage is not then rectified, the cover must be opened and the
foreign body removed manually.
Of backflow: Set the emergency closing device to position »ZU« (Closed) –
Inform specialised company.
Troubleshooting measures
The power supply is automatically taken over by the battery
(approx. 24 hours) until the mains voltage is restored - Safety against
backflow is guaranteed:
– Check mains cable connection and
– Circuit breakers
– Check battery / battery fuse
– Check cabling
Battery voltage has not achieved 13.9 V after 10 hours of charging or
is less than 5 V - no safeguarding against backwater in case of power
outage:
– Replace battery,
Note: In case of backflow, there is a risk of flooding - Set the emer-
gency closing device to position »ZU« (Closed).
Trigger the self-test with T3:
– If the motor doesn't begin immediately, check the cable connections
in the control unit.
If the error message remains, replace the cover (model 4987.418)
– The engine is turning and trying to close the motor-driven flap but
the error message continues: Open and clean cover, see inspection
and maintenance documentation.
If the error message remains, replace the cover.
Forced opening with T3 - keep pressed down for 5 seconds,
replace cover.