DIMeNSIONS AND WeIGHTS
3.5.4 control cabinet installation
3.5.4.1 Mounting instructions
The following mounting materials with the appropriate quality must be used to mount the
drive converter.
required material
Socket screw
Flat washer
Table 41:
required material
Socket screw
Flat washer
Table 42:
3.5.4.2 Mounting distances
Power dissipation for the control cabinet dimension =>
ation of the 400 V devices".
mode/load.
Mounting distances
A
D
B
Figure 12:
Mounting distances
If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriate filters must avoid suction of foreign objects.
ISO 4762
- M6 - 8.8
ISO 7092
- 6 - 200 HV
Mounting instructions for built-in version
ISO 4762
- M5 - 8.8
ISO 7092
- 5 - 200 HV
Mounting instructions for push-through version
A lower value can be used here depending on the operating
reach maximum cooling capacity
For maximum cooling capacity (volume flow), the drive converter must be
mounted without any distance on a smooth, closed mounting plate.
C
D
„Power dissipation at rated oper-
Dimen-
Distance in mm
sion
A
150
B
100
C
30
D
0
X
50
1)
Distance to preceding elements in the control cab-
1)
inet door.
Tightening torque
6.5 Nm
58 lb inch
―
Tightening torque
2.5 Nm
22 lb inch
―
Distance in inch
6
4
1.2
0
2
57