DIMeNSIONS AND WeIGHTS
3.5.3 Push-through version IP54
Housing
Weight
Dimensions
*
Figure 11:
Dimensions push-through version IP54
56
*
*
36
15
290
305
7,5
77,5
150
320
Optional shield connection braket
IP54 zone: Heat sink underneath the mounting plate
For proper installation, the enclosed seal (20F6T45-0001) must be installed
between heat sink and housing (e.g. cabinet wall). The tightness must be
checked after the installation. If properly installed, the separation to the housing
corresponds to degree of protection IP54. However, the fans must be protected
against unfavorable environmental influences. These include combustible, oily
or dangerous fumes or gases, corrosive chemicals, coarse foreign bodies and
excessive dust. This applies especially to the access of the heatsink from the
top (air outlet). Icing is inadmissible.
IP20 zone: Device above the mounting plate
Power connections excluded
is intended for the installation in a suitable housing for the required degree of
protection (e.g. control cabinet).
UL: Device heat sink is classified as NEMA type 1.
*
*
27
6,5
M5
77,5
2
5.2 kg
All dimensions in mm
=> „Climatic environmental
130
292
150
305
conditions"". This part