DEScRIPTION OF THE OPERATOR
3.1 control card block incl. operator
Figure 2:
3.2 Operating conditions
The description of the operating conditions can be found in the instructions for use of the
used COMBIVERT F6 drive converter.
NOTICE
This behaviour can occur for devices of the F6 series with housing 6, 7, 8 and 9. From
the revision levels listed in the table, an operator can be plugged in without regard to the
operating state.
Table 2:
1)
Control card block incl. operator (front panel)
Avoidance of faulty shutdowns
When the operator is plugged into an operational device (supply voltage
and 24 V voltage switched on), the message "42 exception state: ER-
ROR power unit SACB comm." can be displayed.
The error is reset by switching the 24 V voltage of the drive converter off
and on again.
Series
COMBIVERT
F6
Revision levels of the housings
The information on the revision level can be found on the nameplate of the
used COMBIVERT F6 drive converter.
Housing
6
7
8
9
Revision
1)
2K
2V
1K
0P
13