Group 3.17: Fire Mode; Group 3.18: Kwh Pulse Output Settings - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

5.17

Group 3.17: Fire Mode

Index
Parameter
P3.17.1
Fire Mode Password
P3.17.2
Fire Mode Activ. Open
P3.17.3
Fire Mode active closed
P3.17.4
Fire Mode Frequency
Fire Mode Frequency
P3.17.5
Source
P3.17.6
Fire Mode Reverse
P3.17.7
Fire Mode preset freq. 1
P3.17.8
Fire Mode preset freq. 2
P3.17.9
Fire Mode preset freq. 3
V3.17.10 Fire Mode Status
V3.17.11 Fire Mode Counter
Fire Mode Run Indication
P3.17.12
Current
5.18

Group 3.18: kWh Pulse Output Settings

Index
Parameter
P3.18.1
kWh pulse length
P3.18.2
kWh pulse resolution
Table 50. Fire mode parameters
Min
Max
Unit
0
9999
8.00
P3.3.2
Hz
0
8
0
50
0
50
Hz
0
50
0
3
0.0
100.0
%
Table 51. kWh pulse output settings
Min
Max
Unit
50
200
ms
1
100
KWh
69
HVAC400X – APPLICATION MANUAL
Default
ID
Description
1002 = Enabled.
0
1599
1234 = Test mode.
Open = Fire Mode active.
DigINSlot0
1596
.2
closed = No action.
Open = No action.
DigINSlot0
1619
.1
Closed = Fire Mode active.
50.00
1598
0 = Fire Mode frequency.
1 = Preset speeds.
2 = Keypad.
3 = Fieldbus.
0
1617
4 = AI1.
5 = AI2.
6 = AI1 + AI2.
7 = PID1.
8 = Motor potentiometer.
Open = Forward.
DigINSlot0
1618
.1
Closed = Reverse.
10
15535
20
15536
30
15537
A 0 = Disabled.
1 = Enabled.
0
1597
2 = Activated (Enabled + DI
Open).
3 = Test Mode.
0
1679
10.0
15580
Default
ID
Description
50
15534
1
15533
EN2B-0417GE51 R0719

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents