Honeywell HVAC400x Applications Manual page 134

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
A
B
C
D
E
A.
Fault trigger.
B.
Alarm.
C.
Autoreset.
D.
Trial time.
E.
Fault active.
P3.10.6 AUTORESET: UNDERVOLTAGE (ID 720)
You can use this parameter to enable the automatic reset after an undervoltage fault.
P3.10.7 AUTORESET: OVERVOLTAGE (ID 721)
You can use this parameter to enable the automatic reset after an overvoltage fault.
P3.10.8 AUTORESET: OVERCURRENT (ID 722)
You can use this parameter to enable the automatic reset after an overcurrent fault.
P3.10.9 AUTORESET: AI LOW (ID 723)
You can use this parameter to enable the automatic reset after a fault caused by low AI signal.
P3.10.10 AUTORESET: UNIT OVERTEMPERATURE (ID 724)
You can use this parameter to enable the automatic reset after a fault caused by unit overtemperature.
P3.10.11 AUTORESET: MOTOR OVERTEMPERATURE (ID 725)
You can use this parameter to enable the automatic reset after a fault caused by motor overtemperature.
P3.10.12 AUTORESET: EXTERNAL FAULT (ID 726)
You can use this parameter to enable the automatic reset after an external fault.
EN2B-0417GE51 R0719
F
F
G
Fig. 33. The Automatic reset function: (ID759 = 2))
Legend
F
H
I
F.
Wait time ID717.
G.
Reset 1.
H.
Reset 2.
I.
Trial time ID718
134