HVAC400X – APPLICATION MANUAL
Index
Parameter
P3.5.3.2.1
Basic R01 Function
EN2B-0417GE51 R0719
Table 20. Digital output settings on standard I/O board
Min
Max
0
41
Unit
Default
ID
2
11001
50
Description
The function selection for Basic
R01.
0 = None.
1 = Ready.
2 = Run.
3 = Fault.
4 = FaultInvert.
5 = Alarm.
6 = Reverse.
7 = At speed.
8 = Motor regulator active.
9 = Preset speed.
10 = Keypad control.
11 = I/O B control.
12= Limit supervision 1.
13 = Limit supervision 2.
14 = Start signal.
15 = Reserved.
16 = Fire mode activation.
17 = RTC time channel 1 control.
18 = RTC time channel 2 control.
19 = RTC time channel 3 control.
20 = FB ControlWord B13.
21 = FB ControlWord B14.
22 = FB ControlWord B15.
23 = PID 1 in Sleep mode.
24 = Reserved.
25 = PID1 supervision limits.
26 = PID2 supervision limits.
27 = Motor 1 control.
28 = Motor 2 control.
29 = Motor 3 control.
30 = Motor 4 control.
31 = Motor 5 control.
32 = Reserved.
33 = Reserved.
34 = Maintenance alarm.
35 = Maintenance fault.
36 = Thermistor fault.
37 = Motor switch.
38 = PreHeat.
39 = kWh pulse output.
40 = Run Indication.
41 = Selected Param. Set.