Parameter
P3.13.3.1
Feedback Function
P3.13.3.2
Feedback Function Gain
P3.13.3.3
Feedback 1 Source Selection 0
P3.13.3.4
Feedback 1 Minimum
P3.13.3.5
Feedback 1 Maximum
P3.13.3.6
Feedback 2 Source Selection 0
P3.13.3.7
Feedback 2 Minimum
P3.13.3.8
Feedback 2 Maximum
Table 39. Feedback settings
Min
Max
Unit
1
9
-1000.0 1000.0
%
14
-200.00 200.00
%
-200.00 200.00
%
14
-200.00 200.00
%
-200.00 200.00
%
63
HVAC400X – APPLICATION MANUAL
Default
ID
Description
1 = Only Source1 in use.
2 = SQRT(Source1);
(Flow=Constant x
SQRT(Pressure)).
3 = SQRT(Source1- Source 2).
4 = SQRT(Source 1) + SQRT
1
333
(Source 2).
5 = Source 1 + Source 2.
6 = Source 1 - Source 2.
7 = MIN (Source 1, Source 2).
8 = MAX (Source 1, Source 2).
9 = MEAN (Source 1, Source 2).
100.0
1058
0 = Not used.
1 = AI1.
2 = AI2.
3 = AI3.
4 = AI4.
5 = AI5.
6 = AI6.
7 = ProcessDataIn1.
8 = ProcessDataIn2.
2
334
9 = ProcessDataIn3.
10 = ProcessDataIn4.
11 = ProcessDataIn5.
12 = ProcessDataIn6.
13 = ProcessDataIn7.
14 = ProcessDataIn8.
15 = Temp Input 1.
16 = Temp Input 2.
17 = Temp Input 3.
0.00
336
100.00
337
0
335
See P3.13.3.3.
0.00
338
See P3.13.3.4.
100.00
339
See P3.13.3.5.