Group 3.5: I/O Configuration - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

5.5

Group 3.5: I/O Configuration

For more information, see
Index
Parameter
P3.5.1.1
Control signal 1 A
P3.5.1.2
Control signal 2 A
P3.5.1.3
Control signal 1 B
P3.5.1.4
Control signal 2 B
P3.5.1.5
I/O B Control Force
P3.5.1.6
I/O B Reference Force
P3.5.1.7
External Fault Close
P3.5.1.8
External Fault Open
P3.5.1.9
Fault Reset Close
P3.5.1.10
Run Enable
P3.5.1.11
Interlock 1
P3.5.1.12
Interlock 2
Acceleration / Deceleration Time
P3.5.1.13
Set
P3.5.1.14
Motor Preheat ON
P3.5.1.15
Fire Mode Activation OPEN
P3.5.1.16
Preset Frequency Selection 0
P3.5.1.17
Preset Frequency Selection 1
P3.5.1.18
Preset Frequency Selection 2
P3.5.1.19
Timer 1
P3.5.1.20
Timer 2
P3.5.1.21
Timer 3
P3.5.1.22
PID1 Setpoint Boost
10.5.1.1
Programming Digital Inputs.
Table 18. Digital input settings
Min
DigIN SlotA.1
DigIN SlotA.2
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.1
DigIN SlotA.3
DigIN Slot0.2
DigIN SlotA.6
DigIN Slot0.2
DigIN Slot0.2
DigIN Slot0.2
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.2
DigIN SlotA.4
DigIN SlotA.5
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.1
DigIN Slot0.1
HVAC400X – APPLICATION MANUAL
Max
Unit
403
404
423
424
425
343
OPEN = OK.
405
CLOSED = External fault.
OPEN = External fault.
406
CLOSED = OK.
414
407
1041
1042
OPEN = Ramp 1 Shape, Acceleration Time
1 and Deceleration Time 1.
408
CLOSED = Ramp 2 Shape, Acceleration
Time 2 and Deceleration Time 2.
OPEN = No action.
CLOSED = Uses the DC current of the
1044
motor preheat in Stop state. Used when the
value of P3.1.2.5 is 2.
OPEN = Active.
1596
CLOSED = Inactive.
419
420
421
447
448
449
OPEN = No boost.
1046
CLOSED = Boost.
47
EN2B-0417GE51 R0719