Honeywell HVAC400x Applications Manual page 52

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
The Digital Outputs of the Expander Slots C, D, and E
Shows only the parameters for the outputs on option boards in slots C, D and E. Make the selections as in Basic
RO1 Function (P3.5.3.2.1).
If there are no digital outputs in slots C, D, or E, this group or these parameters are not visible.
Index
Parameter
P3.5.4.1.1
AO1 function
P3.5.4.1.2
AO1 filter time
P3.5.4.1.3
AO1 minimum signal
P3.5.4.1.4
AO1 minimum scale
P3.5.4.1.5
AO1 maximum scale
EN2B-0417GE51 R0719
Table 21. Standard I/O board analog output settings
Min
Max
0
20
0.0
300.0
0
1
Varies
Varies
Varies
Varies
Unit
Default
ID
2
10050
s
1.0
10051
0
10052
Varies
0.0
10053
Varies
0.0
10054
52
Description
0 = TEST 0% (Not used).
1 = TEST 100%.
2 = Output freq (0 - fmax).
3 = Freq reference (0 - fmax).
4 = Motor speed (0 - Motor
nominal speed).
5 = Output current (0 - InMotor).
6 = Motor torque (0 - TnMotor).
7 = Motor power (0 - PnMotor).
8 = Motor voltage (0 - UnMotor).
9 = DC link voltage (0 - 1000V).
10 = PID1 output (0-100%).
11 = PID2 output (0-100%).
12 = ProcessDataIn1 (0-100%).
13 = ProcessDataIn2 (0-100%).
14 = ProcessDataIn3 (0-100%).
15 = ProcessDataIn4 (0-100%).
16 = ProcessDataIn5 (0-100%).
17 = ProcessDataIn6 (0-100%).
18 = ProcessDataIn7 (0-100%).
19 = ProcessDataIn8 (0-100%).
20 = PID Feedback (0-100%).
0 = No filtering.
0 = 0 mA / 0V.
1 = 4 mA / 2V.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents