Honeywell HVAC400x Applications Manual page 66

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
Index
Parameter
P3.14.2.1
Keypad Setpoint 1
P3.14.2.2
Keypad Setpoint 2
P3.14.2.3
Setpoint Ramp Time
Setpoint Source 1
P3.14.2.4
Selection
P3.14.2.5
Setpoint 1 min.
P3.14.2.6
Setpoint 1 max.
Setpoint source 2
P3.14.2.7
selection
P3.14.2.8
Setpoint 2 min.
P3.14.2.9
Setpoint 2 max.
EN2B-0417GE51 R0719
Table 45. Setpoints
Min
Max
Varies
Varies
Varies
Varies
0.00
300.0
0
19
-200.00
200.00
-200.00
200.00
0.00
320.00
0
3000
-214748.36
214748.36
66
Unit
Default
ID
Varies
0
1640
Varies
0
1641
s
0.00
1642
1
1643
%
0.00
1644
%
100.00
1645
Hz
0.00
1646
s
0
1647
Varies
0
1648
Description
0 = Not Used.
1 = Keypad Setpoint 1.
2 = Keypad Setpoint 2.
3 = AI1.
4 = AI2.
5 = AI3.
6 = AI4.
7 = AI5.
8 = AI6.
9 =ProcessDataIn1.
10 =ProcessDataIn2.
11 =ProcessDataIn3.
12 =ProcessDataIn4.
13 =ProcessDataIn5.
14 =ProcessDataIn6.
15 =ProcessDataIn7.
16 =ProcessDataIn8.
17 = Temp Input 1.
18 = Temp Input 2.
19 = Temp Input 3.
See P3.14.2.4.