A maintenance counter tells you that the maintenance must be done when the counter value goes above the set
limit.
P3.16.2 COUNTER 1 ALARM LIMIT (ID 1105)
You can use this parameter to set the alarm limit for the maintenance counter.
When the value of the counter goes above this limit, a maintenance alarm occurs.
P3.16.3 COUNTER 1 FAULT LIMIT (ID 1106)
You can use this parameter to set the fault limit for the maintenance counter.
When the value of the counter goes above this limit, a maintenance fault occurs.
P3.16.4 COUNTER 1 RESET (ID 1107)
You can use this parameter to reset the maintenance counter.
10.17

Fire Mode

When Fire mode is active, the drive resets all faults that occur and continues to operate at the same speed until it is
not possible. The drive ignores all commands from the keypad, fieldbuses, and the PC tool.
The Fire mode function has 2 modes, the Test mode and the Enabled mode. To make a selection of a mode, write
a password in parameter P3.17.1 (Fire Mode Password). In the Test mode, the drive does not automatically reset
the faults, and the drive stops when a fault occurs.
NOTE:
This input is normally closed.
When you activate the Fire mode function, an alarm shows on the display.
CAUTION!
!
The warranty is void if the Fire mode function is activated! You can use Test mode to test the Fire mode
function and the warranty will remain valid.
P3.17.1 FIRE MODE PASSWORD (ID 1599)
You can use this parameter to enable the Fire Mode function.
NOTE:
All other Fire Mode parameters will be locked when the Fire Mode is enabled and correct password is set
in this parameter.
Selection number Selection name
1001
Enabled
1234
Test mode
P3.17.2 FIRE MODE ACTIVATION ON OPEN (ID 1596)
You can use this parameter to select the digital input signal that activates the Fire Mode function.
If this digital input signal is activated, an alarm shows on the display, and the warranty becomes void. The type of
this digital input signal is NC (normally closed).
It is possible to try the Fire mode with the password that activates the Test mode. Then the warranty stays valid.
EN2B-0417GE51 R0719
P3.17.1 FIRE MODE PASSWORD (ID 1599)
Description
The drive resets all the faults and continues to operate at the same
speed until it is not possible.
The drive does not automatically reset the faults, and the drive stops
when a fault occurs.